| 21071181 515 N FLAGLER DR # 1500 |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 1.COMPLIED |
| |
| 2. COMPLIED |
| |
| 3. COMPLIED |
| |
| 4. COMPLIED |
| |
| 5. COMPLIED |
| |
| 6. PARTIALLY COMPLIED: SD-2 DUAL CHECK VALVES ARE ASSE |
| 1032 COMPLIANT. PER FBC PL 608.3, 608.17.1.2 AND TABLE |
| 608.1, SAID DEVICES USED IN THE NOTED APPLICATIONS ON |
| THE PLAN SHALL COMPLY WITH ASSE 1024. |
| NEW COMMENT: SUBMITTED ZURN Z-700 IS ASSE 1024 |
| COMPLIANT AS REQUIRED. REVISED KEYNOTE 5 INDICATES ASSE |
| 1022; PER WPB FBC 107.2.1, CORRECT KEYNOTE 5 TO REFLECT |
| ASSE 1024. |
| |
| 7. COMPLIED |
| |
| 8.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A DETAIL |
| SHOWING COMPLIANCE WITH FBC PL 409.4. THE WASTE |
| CONNECTION OF A RESIDENTIAL DISHWASHER SHALL CONNECT |
| DIRECTLY TO A WYE BRANCH FITTING ON THE TAILPIECE OF |
| THE KITCHEN SINK, DIRECTLY TO THE DISHWASHER CONNECTION |
| OF A FOOD WASTE DISPOSER, OR THROUGH AN AIR BREAK TO A |
| STANDPIPE. THE WASTE LINE OF A RESIDENTIAL DISHWASHER |
| SHALL RISE AND BE SECURELY FASTENED TO THE UNDERSIDE OF |
| THE SINK RIM OR COUNTER TOP. |
| PLEASE NOTE, SPECIFIED WALL RECEPTACLE WATER-TITE |
| DW1200HA FOR DISHWASHER IS NOT A COMBINATION WATER |
| SUPPLY/DRAIN RECEPTACLE BOX. |
| |
| 9. COMPLIED |
| |
| 10. COMPLIED |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |