Plan Review Notes
Plan Review Notes For Permit 21071181
Permit Number 21071181
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-12 13:36:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21071181 515 N FLAGLER DR # 1500
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, PROVIDE SIDE ELEVATION DETAIL OF
 NEW SINK. INCLUDE THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC
 606.3, TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC
 306.2 AND 306.3.
  
 2.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 3.PER WPB FBC 107.2.1, NOTE ALL COMPONENTS IN WATER
 SYSTEM SHALL BE LEAD FREE AS REQUIRED IN FBC PL 605.2,
 605.2.1.
  
 4.RE: MOISTURE SENSOR DETAIL; PER WPB FBC 107.2.1,
 PROVIDE WATER HAMMER ARRESTOR TO CONTROL WATER HAMMER
 AT SOLENOID VALVE AS REQUIRED BY FBC PL 604.9.
 ADDITIONALLY SHOW SOLENOID VALVE IN RISER DIAGRAM
  
 5.GENERAL PLUMBING NOTES; NOTE 14 CALLS FOR WATER
 HAMMER ARRESTORS TO BE INSTALLED WHERE QUICK-CLOSING
 VALVES ARE UTILIZED. NOTE PER FBC PL 604.9, WATER
 HAMMER ARRESTORS SHALL COMFORM TO ASSE 1010. NOTE THAT
 THE SPECIFIED WATER-TITE DW1200HA FOR THE DISHWASHER
 COMPLIES AS IT DOES COMFORM TO ASSE 1010. THE
 WATER-TITE AB9700 SPECIFIED FOR THE REFRIGERATOR ICE
 MAKER AND COFFEE MAKER DO NOT COMFORM TO ASSE 1010. PER
 WPB FBC 107.2.1, IF A WALL BOX IS SPECIFIED THAT IS NOT
 ASSE 1010 COMPLIANT, THEN SPECIFY AND SHOW ON THE RISER
 DIAGRAM THE REQUIRED WATER HAMMER ARRESTOR(S).
  
 6.SD-2 DUAL CHECK VALVES ARE ASSE 1032 COMPLIANT. PER
 FBC PL 608.3, 608.17.1.2 AND TABLE 608.1, SAID DEVICES
 USED IN THE NOTED APPLICATIONS ON THE PLAN SHALL COMPLY
 WITH ASSE 1024.
  
 7.PLUMBING KEYNOTE #2: CALLS FOR COLD WATER SUPPLY TO
 DISHWASHER. WATER RISER DIAGRAM CALLS FOR HOT WATER TO
 DISHWASHER. PER WPB FBC 107.2.1, CLARIFY.
  
 8.PER WPB FBC 107.2.1, PROVIDE A DETAIL SHOWING
 COMPLIANCE WITH FBC PL 409.4. THE WASTE CONNECTION OF A
 RESIDENTIAL DISHWASHER SHALL CONNECT DIRECTLY TO A WYE
 BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK,
 DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD WASTE
 DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. THE
 WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE AND
 BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM
 OR COUNTER TOP.
  
 9.PER FBC PL 911.3, TABLE 911.3, THE VERTICAL DRAIN
 BETWEEN THE ADDED SINK AND THE EXISTING LAVATORY SHALL
 BE SIZED A MINIMUM 2 INCH AND SHALL CONTINUE THAT SIZE
 TO CONNECTION WITH THE HORIZONTAL BRANCH. PER WPB FBC
 107.2.1, ADD A NOTE STATING THE NEW SINK AND EXISTING
 LAVATORY ARE COMMON VENTED IN ACCORDANCE WITH FBC PL
 911.
  
 10.REGARDING POINT OF USE WATER HEATER DETAIL:
 ?.A)PER WPB FBC 107.2.1, REVISE ? INCH HW TO ADJACENT
 OR BACK TO BACK FIXTURE TO STATE ? INCH HW TO
 DISHWASHER
 ?.B)COLD WATER TO SINK AND WATER HEATER; PER FBC PL
 606.2 AND 503.1, PROVIDE A TEE BETWEEN THE WALL STUB
 OUT AND THE TWO FIXTURES. PROVIDE A DEDICATED SHUT OFF
 VALVE BETWEEN THE TEE AND SINK. PROVIDE A DEDICATED
 SHUT-OFF VALVE BETWEEN THE TEE AND THE WATER HEATER.
 ?.C)HOT WATER TO SINK AND DISHWASHER; PER FBC PL 606.2,
 PROVIDE A DEDICATED SHUT OFF VALVE BETWEEN THE TEE AND
 SINK.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21071181 515 N FLAGLER DR # 1500
  