2021-08-04 10:00:56 | 08/04/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| 1. THE EXISTING SYSTEM HAS 97 FEET TO THE LONGEST RUN |
| IN CITY RECORDS. IN THE ISOMETRIC SUBMITTED, THERE ARE |
| 20 FEET OF 3/4 INCHES GALVANIZED AND AN EXISTING OF 85 |
| FEET ON A TEE; IT HAS A TOTAL OF 105 FEET. THE 20 FEET |
| 3/4 INCH TO THE METER WHICH HAS A 12-INCH WATER COLUMN |
| MARKED ON IT. IF THIS IS A 2 PSI METER UPGRADE, PLEASE |
| NOTE ON PLANS. THERE SHOULD BE A REGULATOR IN THE |
| EXISTING SYSTEM SHOWN. THE GENERATOR IS AT 1 1/4 |
| INCHES, BUT IT MAY NEED TO BE RESIZED ACCORDING TO THE |
| LONGEST RUN. WOULD YOU PLEASE CLARIFY AND CORRECT PET |
| THE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 2. WHERE REGULATORS ARE INSTALLED, WOULD YOU PLEASE |
| SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |