Plan Review Notes
Plan Review Notes For Permit 21071163
Permit Number 21071163
Review Stop G
Sequence Number 1
Notes
Date Text
2021-08-04 10:00:5608/04/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. THE EXISTING SYSTEM HAS 97 FEET TO THE LONGEST RUN
 IN CITY RECORDS. IN THE ISOMETRIC SUBMITTED, THERE ARE
 20 FEET OF 3/4 INCHES GALVANIZED AND AN EXISTING OF 85
 FEET ON A TEE; IT HAS A TOTAL OF 105 FEET. THE 20 FEET
 3/4 INCH TO THE METER WHICH HAS A 12-INCH WATER COLUMN
 MARKED ON IT. IF THIS IS A 2 PSI METER UPGRADE, PLEASE
 NOTE ON PLANS. THERE SHOULD BE A REGULATOR IN THE
 EXISTING SYSTEM SHOWN. THE GENERATOR IS AT 1 1/4
 INCHES, BUT IT MAY NEED TO BE RESIZED ACCORDING TO THE
 LONGEST RUN. WOULD YOU PLEASE CLARIFY AND CORRECT PET
 THE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. WHERE REGULATORS ARE INSTALLED, WOULD YOU PLEASE
 SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  