2021-09-24 17:15:46 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 4TH REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: RE: SUPPORTING DOC'S FOLDER. I HAVE LOCKED ALL |
| DOCUMENTS THAT ARE DUPLICATE OR NOT RELEVANT TO THIS |
| SUBMITTAL. |
| |
| 1. PROVIDE A SITE PLAN, FLOOR PLAN OR BUILDING SKETCH. |
| IDENTIFY LOCATION OF PROPOSED DOOR. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2. REF. PRODUCT APPROVAL FL 15012-R8 FOR THE FOLLOOWING |
| COMMENTS: |
| |
| THE DESIGN PRESSURES (32.0/-36.2) OF AN 8 FOOT WIDE |
| OVERHEAD DOOR (OHD) ARE INSUFFICIENT FOR THE SITE |
| CONDITIONS. PROVIDE DESIGN PRESSURE CALCULATIONS FOR AN |
| 8 FOOT WIDE OHD THAT MEET OR EXCEED THE DESIGN |
| PRESSURES OF THE SITE. SEE FBC R301. |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4) WITH ADJUSTMENTS PER COEFFECIENTS |
| PER R301.2(3). |
| |
| |
| COMMENTS FROM 1ST REVIEW BY S HILL. |
| |
| 1. SEE FBC R TABLE 301.2(4), A 9' DOOR MODIFIED BY |
| TABLE R301.2(3) HAS A DESIGN PRESSURE REQUIREMENT OF |
| +33.39/-37.75. THE DOOR PRODUCT APPROVAL SUBMITTED HAS |
| A DESIGN PRESSURE LIMITATION OF +32/-36.2 FOR AN 8' |
| DOOR. SINCE DESIGN PRESSURES FOR AN 8' OPENING WIDE |
| GARAGE DOOR IS NOT INCLUDED IN THE FBC, PROVIDE |
| CALCULATIONS TO SHOW DP FOR AN 8' DOOR. A 8' DOOR WILL |
| REQUIRE HIGHER DESIGN PRESSURES THAN A 9' DOOR BUT THE |
| DP REQUIREMENT WILL LIKELY BE VERY CLOSE TO THE SAME AS |
| A 9' WIDE DOOR. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |