Plan Review Notes For Permit 21071160 |
Permit Number |
21071160 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-07-24 10:55:58 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. SEE FBC R TABLE 301.2(4), A 9' DOOR MODIFIED BY | | TABLE R301.2(3) HAS A DESIGN PRESSURE REQUIREMENT OF | | +33.39/-37.75. THE DOOR PRODUCT APPROVAL SUBMITTED HAS | | A DESIGN PRESSURE LIMITATION OF +32/-36.2 FOR AN 8' | | DOOR. SINCE DESIGN PRESSURES FOR AN 8' OPENING WIDE | | GARAGE DOOR IS NOT INCLUDED IN THE FBC, PROVIDE | | CALCULATIONS TO SHOW DP FOR AN 8' DOOR. A 8' DOOR WILL | | REQUIRE HIGHER DESIGN PRESSURES THAN A 9' DOOR BUT THE | | DP REQUIREMENT WILL LIKELY BE VERY CLOSE TO THE SAME AS | | A 9' WIDE DOOR. | | |
|