2021-10-06 14:42:34RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A602 - ACCESSIBLE BAR AREA - THE FOOT RAIL
 SHOWN ON THE "ACCESSIBLE BAR SECTION" WILL NOT COMPLY
 WITH THE REQUIRED TOE CLEARANCE PER FBC A 306.2.2
 MAXIMUM DEPTH.
 TOE CLEARANCE SHALL EXTEND 25 INCHES (635 MM) MAXIMUM
 UNDER AN ELEMENT.
  
 2) ACCESSIBLE RESTROOM - TO AVOID MISPLACEMENT OF THE
 FRAMED MIRROR - PLEASE STATE THAT THE HEIGHT FROM THE
 FINISHED FLOOR TO THE BOTTOM OF THE OF THE MIRROR IS TO
 THE"REFLECTIVE SURFACE" FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
  
  
  
  
  