2021-08-28 07:52:33 | THERE IS NO REAPONSE LETTER OR REVISED MECHANICAL |
| DRAWINGS SUBMITTED FOR THIS CYCLE OF REVIEW. PLEASE |
| PROVIDE A RESPONSE LETTER AND REVISED DRAWINGS |
| ADDRESSING THE 1ST CYCLE COMMENTS LISTED BELOW. |
| |
| 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21071035 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE |
| HOODS WILL REQUIRE A SEPARATE APPLICATION, REVIEW AND |
| DRAWINGS. THE HOODS WILL NOT BE REVIEWED UNDER THIS |
| PERMIT. |
| |
| 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE |
| REFRIGERATION WILL REQUIRE A SEPARATE APPLICATION, |
| REVIEW AND DRAWINGS. THE REFRIGERATION WILL NOT BE |
| REVIEWED UNDER THIS PERMIT. |
| |
| 3) SHEET M2.2: IT APPEARS THAT THE ROOM LABELED CLOSET |
| IS BEING USED FOR A RETURN AIR PATH. RETURN AIR SHALL |
| NOT BE TAKEN FROM A CLOSET. FBC M 601.5 (7) |
| |
| 4) PLEASE PROVIDE A MECHANICAL FLOOR PLAN FOR THE |
| RESTAURANT. FBC 107.2.1 |
| |
| 5) THE MINIMUM REQUIRED OUTDOOR AIR FOR THE DINING ROOM |
| IS 2504 CFM; THE KITCHEN MINIMUM OUTDOOR AIR IS 434 |
| CFM. FBC 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |