Plan Review Notes
Plan Review Notes For Permit 21071035
Permit Number 21071035
Review Stop B
Sequence Number 2
Notes
Date Text
2021-09-20 13:24:28RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE
 SWING DOORS. STORE FRONT DOORS ARE NOT PART OF THE
 PRODUCT APPROVAL (FL14218) FOR THE STOREFRONT WINDOWS.
  
 2) DRAWING A602 HAS NOT BEEN REVISED - THE ACCESSIBLE
 BAR COUNTER CANNOT BE PORTABLE AS SHOWN ON DRAWING A602
 DETAIL 2. (PER THE BUILDING OFFICIALS INTERPRETATION)
 FBC A902
  
 3) REVISED DRAWING A601 IS VERSIONED ON TOP OF A602 IN
 PROJECTDOX - PLEASE CORRECT
  
 4) PLEASE SHOW THE KNEE AND TOE CLEARANCE FOR THE
 ACCESSIBLE SEATING AT THE BARS PER FBC 902.2
  
 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE HEIGHT FROM
 THE FINISHED FLOOR TO THE BOTTOM OF THE "REFLECTIVE
 SURFACE" OF THE MIRROR FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 6) ACCESSIBLE RESTROOM - PLEASE SHOW THE PAPER TOWEL
 DISPENSER OUTLET HEIGHT FROM THE FLOOR TO COMPLY WITH
 FBC 308
  
 7) ACCESSIBLE RESTROOM - PLEASE SHOW THE REAR TOILET
 GRAB BAR DIMENSIONS FROM THE CENTER OF THE TOILET PER
 FBC 604.5.2
  
 8) PLEASE SHOW THE CLEAR RAMP LANDING LENGTH (5') AT
 THE TOP OF THE REAR ACCESSIBLE RAMP FBC 405.7
  
  