Plan Review Notes
Plan Review Notes For Permit 21071035
Permit Number 21071035
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-23 18:04:3308/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON A001, UNDER GENERAL NOTES, # 1 HAS 2017, AND IT
 SHOULD BE 2020 PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET A003;
  
 A. THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE 4
 INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC.
 603.3.
  
 B. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER THE 2020 FBC ACC SEC. 609.4.
  
 C. THE TOILET PAPER DISPENSERS SHALL BE 7 INCHES
 MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER PER
 THE 2020 FBC ACC SEC. 604.7.
  
 D. WOULD YOU, PLEASE SHOW THE 30 INCHES BY 48 INCHES
 INSIDE THE RUNNING RADIUS PER THE 2020 FBC ACC SEC. 305
 CLEAR FLOOR OR GROUND SPACE.
  
 3. ON SHEET A150, UNDER GENERAL DEMOLITION NOTES, # 2
 HAS 2017, AND IT SHOULD BE 2020 PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. ON SHEETS A201 A251 AND A 801; THE STALL IN THE
 WOMEN AND MEN'S RESTROOM DOES NOT SHOW A WATER CLOSET;
  
 A. PLEASE PROVIDE THE CLEAR FLOOR SPACE FOR THE TOILET
 THAT WILL BE IN THE TOILET STALL, URINAL, AND LAVS
 OUTSIDE STALL PER THE FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE.
  
 B. PLEASE SHOW ALL CLEAR FLOOR SPACE DIMENSIONS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE.
  
 5. ON SHEET A250, UNDER PLUMBING FIXTURES TABLE 2017,
 IT SHOULD BE 2020 PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 THERE ARE TWO OR MORE LOCATIONS WITH 2017 ON AS WELL.
  
 6. ON SHEET A801;
 A. ON FIXTURE ELEVATION, THE TOILET SHALL BE 1 FOOT 6
 INCHES TO 1 FOOT 8 INCHES AND ONLY 1 FOOT 6 INCHES
 SHOW. WOULD YOU PLEASE ADD THE VARIANCE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THE WATER CLOSET IN THE BACK WALL GRAB BAR SHALL BE
 1 INCHES FROM THE CENTER OF THE WATER CLOSET TO THE
 SIDE OF THE GRAB BAR AND 2 FEET TO THE OTHER SIDE PER
 THE 2020 ACC 604.5.2 REAR WALL.
  
 C. WOULD YOU PLEASE SHOW THE BOTTOM ON THE LAV, WHICH
 SHALL BE A MINIMUM OF 27 INCHES KNEE CLEARANCE PER THE
 2020 FBC SEC. 306.3.
  
 D. THE WATER CLOSET CONTROL FLUSH SHALL BE ON THE OPEN
 SIDE CONTROL PER THE 2020 FBC SEC. 604.6 FLUSH
 CONTROLS.
  
 E. HANDICAP CAP WATER CLOSET FLUSH CONTROL SHALL BE
 HAND OPERATED OR AUTOMATIC AND SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND ON THE OPEN SIDE PER
 THE 2020 FBC ACC SEC. 604.9.5.
  
 F. WOULD YOU, PLEASE SHOW THE CLEAR FLOOR SPACE SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDEWALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1.
  
 G. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 H. PLEASE SHOW OR MENTION THAT THE DOOR HANDLE HARDWARE
 SHOULD BE ON BOTH SIDES OF THE DOOR PER THE 2020 FBC
 ACC SEC. 404.2.7.
  
 I. WOULD YOU PLEASE SHOW THE HEIGHT OF THE PARTITION OF
 THE URINAL PER THE 2020 FBC SEC. P 405.3.5.
  
 J. WOULD YOU PLEASE SHOW THE HEIGHT OF THE LAV IN THE
 OPEN AREA AT 34 INCHES MAXIMUM PER THE 2020 FBC ACC
 SEC. 606.3.
  
 K. WOULD YOU, PLEASE SHOW THE MIRROR'S REFLECTIVE PART,
 WHICH NEEDS TO BE 4 INCHES TO THE REFLECTIVE SIDE PER
 THE 2020 FBC ACC SEC. 603.3.
  
 L. WATER CLOSET COMPARTMENT SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR 604.8.1.7 WATER CLOSET.
  
 7. ON SHEET P.01;
 A.. UNDER PLUMBING NOTES 31, IT HAS THE 6 TH EDITION
 MENTION. THE 7 TH EDITION IS THE CORRECT ONE. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 C. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 D. SODA MACHINES SHALL BE EQUIPPED WITH AN IN-LINE
 VACUUM BREAKER THAT COMPLIES WITH ASSE 1022 PER THE
 2020 FBC SEC. 608.17.1.1.
  
 E. WOULD YOU PLEASE DELETE OR STRIKE THROUGH THE
 ECLECTIC WATER COOLER WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET P0.2;
 A. WOULD YOU PLEASE PROVIDE DETAIL FOR THE FOOD
 HANDLING THREE-COMPARTMENT W/AIR GAP PER THE 2020 FBC
 SEC. P 802.1.1.
  
 B. THE GAS DETAIL SHOWS A CONDENSATE NEUTRALIZER THAT
 IS NOT PERMITTED PER THE AJH IN THE CITY OF WEST PALM
 BEACH AS IT IS NEVER KEPT OR MAINTAINED. WOULD YOU
 PLEASE SHOW WHERE THE CONDENSATE WILL DRAIN AND PLEASE
 SEPARATE CONDENSATE TO DUMP TO A LOCATION IN A SAFE
 PLACE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE SHOW ON THIS PAGE THE ISOMETRIC THE
 SHUT OFF VALVES ON EACH SIDE OF THE RECALCULATING PUMP
 PER THE 2020 FBC SEC. 606.2 LOCATION OF SHUTOFF VALVES.
  
 9. ON SHEET P2-1 AND P3-1;
 A. IN THE BAR AREA SHOWS BAR SINKS AND ICE MACHINES
 INTO THE GREASE INTERCEPTOR THAT IS NOT WASTER AND DO
 NOT REQUIRE TREATMENT AND ARE NOT APPROVED PER THE 2020
 FBC SEC. P1003.2.
  
 B. IN THE RESTAURANT OTHER THAN THE BAR AREA, THERE ARE
 SEVERAL HAND SINKS K 15, B16, B46, K87, AND ICE
 BIN/CUBER K38, B10, AND B4 INTO THE GREASE INTERCEPTOR
 THAT ARE NOT WASTER AND DO NOT REQUIRE TREATMENT, AND
 ARE NOT APPROVED PER THE 2020 FBC SEC. P1003.2.
  
 C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 D. SODA DRINKING BEVERAGE MACHINES SHALL BE PROTECTED
 WITH A DEVICE THAT COMPLIES WITH ASSE 1022 SHALL HAVE
 CARBONATED DISCHARGED TO A SAFE LOCATION PER THE 2020
 FBC SEC. P 608.17.1.1.
  
 E. THE COFFEE MAKER/ICE MAKER REQUIRES AN INLINE VACUUM
 BREAKER THAT COMPLIES WITH THE ASSE 1024 NON-CARBONATED
 PER THE 2020 FBC SEC. 608.17.1.2.
  
 10. ON SHEET P6.1;
 A. HOT WATER LINES NOT IN CONDITION SPACE IN THE GROUND
 NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020
 FBC SEC. RE 403.5.3.
  
 B. THE LINES TO EACH FIXTURE FROM THE RECIRCULATING
 MANIFOLD TO THE HOT WATER LINES SHALL BE SUPPLIED TO
 THE SOURCE; PLEASE REFER TO THE 2020 FBC ENERGY CODE
 TABLE C404.5.1. MAXIMUM ALLOWABLE PIPE LENGTH METHOD.
  
 C. IN THE KEYNOTES, TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2020
 FBC SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
  
 D. THE PIPING SHALL BE INSULATED TO LEVELS SHOWN IN
 TABLE C403.2.10 PER THE 2020 FBC EC 404.4 INSULATION OF
 PIPING.
  
 E. IN THE KITCHEN AREA, THERE IS A THREE-COMPARTMENT
 SINK. PLEASE PROVIDE DETAIL ON THE DRAINS TO AN
 INDIRECT WASTE INDEPENDENTLY FROM EACH OTHER PER THE
 2017 FBC SEC. P 802.1.1.
  
 F. THERE IS TWO GAS UNIT FOR GAS UP ON THE MEZZANINE
 THAT MAY REQUIRE VENTING AND CONDENSATION. WOULD YOU
 PROVIDE MANUFACTURE SPECIFICATION ON HOW THESE ITEM IS
 BEING EXTORTED OUT THE STRUCTURE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 11. ON SHEET A001 IN THE SHEET INDEX, IT CALLS OUT FOR
 SHEET P3.2 MEZZANINE PLUMBING PLAN, AND NONE WAS FOUND.
 WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. IT MENTIONS A GREASE INTERCEPTOR. WOULD YOU PLEASE
 PROVIDE THE CAPACITY OF THE EXISTING INTERCEPTOR IN
 GALLONS?
 A. IS IT SHARED WITH OTHER RESTAURANTS, AND IF SO, WHAT
 IS THEIR VOLUME.
 B. IS IT A PASSIVE HYDRO-MECHANICAL - OR GRAVITY-TYPE
 GREASE INTERCEPTOR MADE OF CONCRETE STEEL OR
 FIBERGLASS?
 C. IF APPLICABLE, WOULD YOU PLEASE PROVIDE THE STANDARD
 BEING USED FOR SIZING OF THE GREASE INTERCEPTOR? THE
 INTERCEPTOR SHALL BE SIZED IN ACCORDANCE WITH ONE OF
 THE STANDARDS LISTED IN 2020 FBC SEC. P 1003.3.5 OR
 RULE 64E-6 OF THE FLORIDA ADMINISTRATIVE CODE AND THE
 CITY OF WEST PALM BEACH STANDARD DETAIL GS-7.
  
 13. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING
 THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE
 COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 PLEASE FEEL FREE TO CONTACT ME ON ANY OF THE COMMENTS
 BY PHONE OR ZOOM MEETING IF YOU LIKE.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  