Plan Review Notes
Plan Review Notes For Permit 21071035
Permit Number 21071035
Review Stop M
Sequence Number 1
Notes
Date Text
2021-08-16 07:50:231ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071035
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 HOODS WILL REQUIRE A SEPARATE APPLICATION, REVIEW AND
 DRAWINGS. THE HOODS WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 REFRIGERATION WILL REQUIRE A SEPARATE APPLICATION,
 REVIEW AND DRAWINGS. THE REFRIGERATION WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 3) SHEET M2.2: IT APPEARS THAT THE ROOM LABELED CLOSET
 IS BEING USED FOR A RETURN AIR PATH. RETURN AIR SHALL
 NOT BE TAKEN FROM A CLOSET. FBC M 601.5 (7)
  
 4) PLEASE PROVIDE A MECHANICAL FLOOR PLAN FOR THE
 RESTAURANT. FBC 107.2.1
  
 5) THE MINIMUM REQUIRED OUTDOOR AIR FOR THE DINING ROOM
 IS 2504 CFM; THE KITCHEN MINIMUM OUTDOOR AIR IS 434
 CFM. FBC 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  