2021-08-24 09:28:48 | 08/24/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET P6.1; |
| A. WOULD YOU PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS |
| OF PIPE PER 2020 FBC FG SECS. 402.4.1, 402.4.2. |
| |
| B. THE REFERENCE CODE IS SHOWING 2017, AND THE CURRENT |
| IS 2020. WOULD YOU PLEASE CORRECT PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS? |
| |
| C. WOULD YOU PLEASE SHOW THE TYPE OF GAS (LP OR |
| NATURAL) PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| D. MOST TANK-LESS UNITS CALL FOR A 10.5 INCHES WATER |
| COLUMN, AND THE SERVICE METER DISCHARGES IS A 12 INCH |
| WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| THE MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| SEC. 410.1. |
| |
| E. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING |
| DETAILS OF THE GAS VENT(S) FOR TANK-LESS PER THE 2020 |
| FBC FG SECS. 502 THRU 505. |
| |
| F. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC. |
| 305.1. |
| |
| G. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| REGULATOR 1' (FOOT) OF EITHER SIDE PER THE 2020 FBC FG |
| SEC 410.2. |
| |
| H. WOULD YOU PLEASE LABEL AND SHOW DRIP LEG IS REQUIRED |
| BEFORE THE EQUIPMENT IS INSTALLED AT TWO POINTS PER THE |
| 2020 FBC FG 408.2 OR 2020 FBC RES. SEC. G2419.2. |
| |
| I. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE |
| BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS. |
| 10.4, 10.5 OF NFPA 96-08. |
| |
| K. THERE IS A SECTION OF PIPE THAT DOES NOT HAVE SIZE. |
| IS IT 1 1/4 INCHES OR 1 1/2 INCHES? WOULD YOU PLEASE |
| CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |