2021-08-24 09:28:4808/24/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P6.1;
 A. WOULD YOU PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS
 OF PIPE PER 2020 FBC FG SECS. 402.4.1, 402.4.2.
  
 B. THE REFERENCE CODE IS SHOWING 2017, AND THE CURRENT
 IS 2020. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. WOULD YOU PLEASE SHOW THE TYPE OF GAS (LP OR
 NATURAL) PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. MOST TANK-LESS UNITS CALL FOR A 10.5 INCHES WATER
 COLUMN, AND THE SERVICE METER DISCHARGES IS A 12 INCH
 WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER
 THE MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. 410.1.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING
 DETAILS OF THE GAS VENT(S) FOR TANK-LESS PER THE 2020
 FBC FG SECS. 502 THRU 505.
  
 F. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC.
 305.1.
  
 G. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' (FOOT) OF EITHER SIDE PER THE 2020 FBC FG
 SEC 410.2.
  
 H. WOULD YOU PLEASE LABEL AND SHOW DRIP LEG IS REQUIRED
 BEFORE THE EQUIPMENT IS INSTALLED AT TWO POINTS PER THE
 2020 FBC FG 408.2 OR 2020 FBC RES. SEC. G2419.2.
  
 I. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08.
  
 K. THERE IS A SECTION OF PIPE THAT DOES NOT HAVE SIZE.
 IS IT 1 1/4 INCHES OR 1 1/2 INCHES? WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  