2021-08-31 16:07:49RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21070963
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- NEW BEDROOM EGRESS WINDOWS DOESN'T SEEM TO COMPLY
 WITH SEC. R310.2.1 FBC-RESIDENTIAL. TYPICALLY, 5'-0"
 SINGLE HUNG IMPACT WINDOW DOESN'T PROVIDE THE REQUIRED
 24" HEIGHT CLEARANCE. REVISE SIZE OF SINGLE HUNG WINDOW
 OR PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE
 5'-0" HIGH WINDOW PROVIDE THE REQUIRED. CLEAR HEIGHT.
  
 2- EXISTING BEDROOM LOCATED ON SOUTH SIZE OF PROPOSED
 HALL.
 THIS BEDROOM USED TO HAVE AN EGRESS DOOR LEADING TO THE
 OUTSIDE. THE DOOR WAS REMOVED TO ALLOW FOR THE NEW
 ADDITION. SPECIFY SIZE AND TYPE OF EXISTING BEDROOM
 WINDOW TO REMAIN TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
  
 3- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT
 IS SPECIFYING R-30 CLOSED CELL SPRAYED INSULATION UNDER
 THE METAL ROOF. PROVIDE ICC EVALUATION REPORT FOR THE
 R-30 INSULATION IN THIS ROOFING SYSTEM TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 4- ARCHITECT TO REVISE STUCCO THICKNESS SPECIFIED ON
 THE BUILDING SECTIONS. NEED TO SPECIFY THE 7/8" MIN.
 STUCCO THICKNESS AS REQUIRED BY TABLE R702.1(1).
 FBC-RESIDENTIAL.
  
 5- ARCHITECT NEEDS TO SPECIFY TWO WATER RESISTIVE
 BARRIERS WHEN STUCCO IS APPLIED TO WOOD AS REQUIRED BY
 SEC. R703.7.3 FBC-RESIDENTIAL.
  
 6- THERE IS A POOL IN THIS PROPERTY. PROVIDE
 SPECIFICATIONS SHOWING HOW THE ADDITION WILL COMPLY
 WITH THE RESIDENTIAL SWIMMING BARRIER REQUIREMENTS.
 SEC. R4501.17.1.9 FBC-RESIDENTIAL.
  
 7- ENERGY CALCULATIONS SUBMITTED:
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 C)REVISE ITEM #2 ON PAGE 1 OF 2. THE ANSWER IS
 INCORRECT. THE QUESTION IS IF THIS IS A SINGLE FAMILY
 OR MULTIPLE FAMILY? DETACHED
 IS NOT THE CORRECT ANSWER. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)REVISE ITEM #11 ON PAGE 1 OF 4. ACCORDING TO PLANS.
 THE ATTIC IS NOT VENTED. SEE PLANS AND REVISE AS
 REQUIRED. ALSO, REVISE THE TYPE OF INSULATION ON PAGE 2
 OF 4. IT IS FOAM INSULATION NOT BATT INSULATION.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)REVISE ROOF MATERIAL ON PAGE 2 OF 4. THERE ARE NO
 SHINGLES ON THIS ADDITION. IT IS METAL ROOFING. SEE
 PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE
 3 OF 4 TO MATCH PLANS. SEE PLANS AND REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,