2021-07-27 06:08:251) SUBMIT MANUFACTURER'S SPECIFICATION SHEETSS FOR ALL
 GAS APPLIANCES. GAS APPLIANCES SHALL BE LISTED AND
 LABELED PER FBC-FUEL GAS SEC.301.3.
 2) THE REFERENCED TABLE ON THE PLANS FOR THE PE PIPE IS
 FOR A 2 PSI SYSTEM YET THE PLANS SHOW A 12 INCH WATER
 COLUMN. CLARIFY.
 3) SHOW THE DEVELOPED LENGTH OF THE SYSTEM FROM THE GAS
 METER TO THE MOST REMOTE OUTLET ON THE SYSTEM. FBC-GAS
 SEC.402.4.
 4) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE GAS
 APPLIANCES. THE DRYER MAY REQUIRE COMBUSTION AIR IF
 LOCATED IN A ROOM WITH A DOOR. SUBMIT CALCULATIONS FOR
 COMBUSTION AIR PER THE FBC-RES. SEC.G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692