Plan Review Notes
Plan Review Notes For Permit 21070873
Permit Number 21070873
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-22 12:09:501ST REVIEW FBC-2020 RES. BUILDING.
 PERMIT- 21070873
 7/23/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE LIMITATIONS NOTE 5.7.2 ON PAGE 4 OF THE
 EVALUATION REPORT REPORT FOR THE ROOFING SYSTEM. THE
 SELECTED W-1 SYSTEM SHOWS AN MDP OF -52.5 PSF WHICH
 APPEARS TO BE INADEQUATE BASED ON THE ENGINEERED WIND
 PRESSURE CALCULATIONS FOR THE BUILDING THAT ARE SHOWN
 ON SHEET S4.2 OF THE APPROVED PLANS UNDER PERMIT
 2101099. USING THE 10 SQ. FT. EFFECTIVE WIND AREA AS
 PROVIDED IN THE CALCULATION TABLE, PRIME ZONE 1 IS
 INDICATED TO BE -57.0 PSF. PLEASE SELECT A SYSTEM
 DESIGN THAT MEETS COMPLIANCE AND RESUBMIT THE COMPLETE
 PRODUCT APPROVAL OR NOA.
  
 2) REFER TO SECTIONS 107.3.4 AND 107.3.4.1 WPB
 AMENDMENTS TO THE FBC. AS STATED IN THE SECTIONS, THE
 DEFERRED ROOFING SYSTEM SUBMITTALS SHALL BE REVIEWED
 AND NOTED, OR STAMPED AS APPROVED BY THE DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE OF THE MAIN BUILDING
 PROJECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  