Notes
Date Text
2021-11-05 08:17:4411/05/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE TIE-DOWN DRAWING BELONG TO A PERSON THAT DOES
 NOT HAVE A ENGINEER STAMP ON IT AND IS NOT ACCEPTABLE.
 THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005. VISIT
 HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO
 PROVIDE THIS DOCUMENT THAT IS ENGINEERED FOR THIS
 APPLICATION.
  
 2. ON THE ISOMETRIC THE PHYSICAL ADDRESS OF THE
 RESIDENCE MUST BE ON PLANS IN FULL, NUMBER, STREET,
 CITY, STATE, AND ZIP CODE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2.
  
 4. IF THE LP-GAS CONTAINERS OR SYSTEMS THAT ARE
 INSTALLED IS WITHIN 10 FT OF PUBLIC VEHICULAR
 THOROUGHFARES IT SHALL BE PROVIDED WITH A MEANS OF
 VEHICULAR BARRIER PROTECTION PER THE 2020 NFPA 58-17
 SEC. 6.8.1.2. DISTANCE IS NEEDED TO DETERMINE THIS.
  
 5. A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS
 TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE
 MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD PER
 THE 2020 FBC FG SEC.G2408.1.
  
 6. WOULD YOU PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (BBQ
 GRILL, POOL HEATER AND FUTURE FIRE PIT) TO VERIFY
 COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC FG SECS. 402.2 AND 301.3 OR 2020 FBC RES. SEC.
 G2413.2 AND G2404.3.
  
 8. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 9. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5.
  
 10. WOULD YOU PLEASE LABEL DRIP LEG PER THE 2020 FBC
 RES. SEC. G2419.2.
  
 11. WOULD YOU PLEASE LABEL HARD CAP FOR FUTURE FIRE PIT
 ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2401.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  