Plan Review Notes
Plan Review Notes For Permit 21070798
Permit Number 21070798
Review Stop G
Sequence Number 1
Notes
Date Text
2021-10-25 07:05:461ST REVIEW FBC-2020 PLUMBING
 PERMIT-21070798
 10/25/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED
  
 1) CLEARLY, INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF
 REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE
 ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND,
 THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2) THE SUBMITTED GAS PERMIT APPLICATION STATES INSTALL
 500 GALLON LP TANK AND GAS LINES TO POOL HEATER, FIRE
 PIT, AND FIRE BOWLS. PLEASE SHOW THE GAS LINES
 EXTENDING TO THE FIRE BOWLS.WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & A
 NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
  
 4) THE SUBMITTED SHEET FOR THE LOCATION OF UNDERGROUND
 LP TANK INSTALLATION IS FOR ILLUSTRATIVE PURPOSES ONLY.
 THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY
 WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF
 THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE.
  
 5) SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY
 WITH NFPA 58 SEC. 6.6.6.1.
  
 6) THE GAS HAS BEEN SUBMITTED THAT IS DRAWN IN PENCIL
 ON THE SURVEY ARE ILLEGIBLE, AND DO NOT SHOW ALL OF THE
 GAS LINES TO BE INSTALLED. PLANS DONE IN PENCIL ARE
 UNACCEPTABLE AS THE DRAWING CAN BE MODIFIED/CHANGED.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1.4 QUALITY OF
 BUILDING PLANS.
  
 7) THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8) A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS
 TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE
 MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD,
 2017 FBC FG SEC.G2408.1.
  
 9) SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRIL AND
 ALL GAS FIXTURES/ APPLIANCES TO BE INSTALLED. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
 10) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  