2021-07-23 07:34:58 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| REF. PRODUCT APPROVAL FOR THE FOLLOWING COMMENTS: |
| |
| 1. ANCHOR SCHEDULE SPECIFIES ANCHOR TYPES A, A1 AND C. |
| ANCHOR SPACING TABLE SPECIFIES ANCHOR TYPES A, A1 AND |
| B. PLEASE CLARIFY? |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| REF. SHUTTER SCHEDULE FOR THE FOLLOWING COMMENTS: |
| |
| 2. SHUTTER INSTALLATION SPECIFIES HORIZONTAL, ACCORDION |
| SHUTTERS ARE INSTALLED VERTICAL. (BLADE ORIENTATION) |
| PLEASE REVIEW AND CORRECT. |
| |
| 3. ANCHOR TYPE. SEE NOTE 1, ANCHOR TYPES SHALL BE |
| SPECIFIC. INCLUDE ALL ANCHOR TYPES USED. A, A1 AND C. |
| |
| 4. SEE SPECIFIC ANCHOR TYPE COLUMN. OPENING #1 SHOULD |
| SPECIFY ANCHOR TYPE C FOR TOP CONNECTION (WOOD) AND |
| ANCHOR TYPE A OR A1 FOR BOTTOM (CONCRETE) CONNECTION. |
| ANCHOR TYPE MUST BE SPECIFIC. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |