2021-07-26 16:29:13 | 1ST REVIEW FBC-2020 RES. GAS | | PERMIT- 21070725 | | 7/26/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) GAS RISER: BASED ON THE PIPE SIZING TABLE ON THE | | DRAWING- TABLE 402.4(1) FBC FG, THE 1-INCH PIPE IS | | UNDERSIZED TO SUPPLY THE TOTAL 594,000 BTUH SYSTEM | | WHICH HAS A TOTAL DEVELOPED LENGTH OF 85 FT. THE PIPE | | SIZE MUCH BE INCREASED, OR THE DELIVERY PRESSURE AT THE | | METER MUST BE INCREASED TO HANDLE THE NEW GENERATOR | | LOAD. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|