Plan Review Notes
Plan Review Notes For Permit 21070725
Permit Number 21070725
Review Stop G
Sequence Number 1
Notes
Date Text
2021-07-26 16:29:131ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21070725
 7/26/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: BASED ON THE PIPE SIZING TABLE ON THE
 DRAWING- TABLE 402.4(1) FBC FG, THE 1-INCH PIPE IS
 UNDERSIZED TO SUPPLY THE TOTAL 594,000 BTUH SYSTEM
 WHICH HAS A TOTAL DEVELOPED LENGTH OF 85 FT. THE PIPE
 SIZE MUCH BE INCREASED, OR THE DELIVERY PRESSURE AT THE
 METER MUST BE INCREASED TO HANDLE THE NEW GENERATOR
 LOAD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  