2021-10-26 15:32:40 | RESIDENTIAL (R3) NEW ACCESSORY STRUCTURE, BUILDING |
| AUDIT. |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21070716 |
| |
| 1- USE ACCESSORY STRUCTURE IS NOT CLEAR. SEC. 107.2.1 |
| CITY AMENDMENTS. FLOOR PLANS SHOW AN ACCESSORY BUILDING |
| FOR WORK SHOP AND STORAGE, WHILE SURVEY SHOWS A GARAGE |
| BUILDING. ALL CONSTRUCTION PLANS NEED TO MATCH. |
| NOTE: THERE IS ALSO, SOME CONFUSION BECAUSE ZONING IS |
| APPROVING A GARAGE CONSTRUCTION NOT AN ACCESSORY |
| STRUCTURE. SEE ZONING REVIEW STAMP ON SURVEY SUBMITTED. |
| REVISE AS REQUIRED. |
| |
| 2- BUILDING DIMENSIONS SHOWN ON THE FLOOR PLAN AND |
| BUILDING DIMENSIONS SHOWN ON THE SURVEY DON'T MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. REVISE AS REQUIRED. |
| |
| 3- SHEET 3-3: ROOF SHEATHING INFORMATION IS NOT CLEAR. |
| INFORMATION ON PLYWOOD ROOF SHEATHING NOTES A AND C, |
| COMPONENTS AND CLADDING PRESSURE ZONES CHART AND NOTE |
| ON THE RIGHT SIDE OF THE ROOF DIAGRAM DOESN'T MATCH. |
| REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| A) WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO AVOID DELAYS/CONFLICTS). |
| |
| B)PEEL AND STICK SHINGLES UNDERLAYMENT SPECIFIED ON |
| PLANS. |
| |
| 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 6- CLARIFY WHY SUBMITTING LINTEL NOA 20-0630.15 FOR |
| 4",6" OR 12" LINTELS IF THIS TYPE OF LINTEL IS NOT |
| SPECIFIED ON PLANS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |