Plan Review Notes
Plan Review Notes For Permit 21070688
Permit Number 21070688
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-11 14:37:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21070688
 ADD: 5600 N FLAGLER DR. # 1604
 CONT: FLAGLER BUILDING SYSTEMS
 TEL: 561-596-3983
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 11TH/ 2021
 ACTION: DENIED
  
 1) SITE SPECIFIC DESIGN PRESSURES REPORT HAS PRESSURES
 FOR WINDOWS 1-3 AND SLIDERS D1 & D2 ON THIS REPORT THEY
 ARE CORRECT. THE SUBMITTED FLOOR PLAN HAS THE SAME
 PRESSURE CHART. THE ISSUE IS ABOVE EACH OPENING THERE
 IS A SECOND SET OF PRESSURES ARE 15 -20 PSF LOWER THAN
 IN THE CHARTS. THE PRESSURES IN THE CHARTS MATCH THAT
 OF FRANK BENNARDO P. E. W/ ENGINEERING EXPRESS.
  
 2) THE CONDO UNIT IT IS ASSUMED IS IN WALL ZONE 4 SINCE
 THERE IS NO FOOTPRINT OF THE BUILDING SHOWING THE UNIT
 WITHIN THE FOOTPRINT. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 3) SHEET 001 NOTES SCOPE OF WORK NOTE # 3 INDICATES
 TILE FLOORING REPLACED W/ WHISPER MAT UNDERLAYMENT PER
 CODE.
 THE NOTE DOES NOT INDICATE WHAT TYPE OF MATERIAL IS
 GOING BACK AS A FINISH FLOOR NOR DOES THE DESIGNER OF
 RECORD IDENTIFY
 WHICH TYPE OF WHISPER MAT CS OR HW TO BE INSTALLED.
 107.2.1.2.
  
 4) PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  