Plan Review Notes
Plan Review Notes For Permit 21070571
Permit Number 21070571
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-24 09:48:10PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 REF. SHUTTER SCHEDULE FOR THE FOLLWING:
  
 1. TYPE OF ANCHOR-LIST ALL ANCHOR TYPES TO BE USED
 (CONSTRUCTION TYPES-CONCRETE AND WOOD)
  
 2. VERIFY EDGE DISTANCE AND SPACING PER ANCHOR SCHEDULE
 PG 13 OF 13 IN PRODUCT APPROVAL.
  
 REF. PRODUCT APPROVAL FOR THE FOLLWING:
  
 3. PER ANCHOR SCHEDULE, PG. 13 OF 13, CRETEFLEX TAPCONS
 ARE NOT ALLOWED FOR INSTALLATION INTO WOOD.
  
 4. PER ANCHOR SCHEDULE, PG 13 OF 13, MINIMUM EDGE
 DISTANCE OF CRETEFLEX ANCHORS SHALL BE 3 INCHES.
  
 PLEASE CLARIFY
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.