Plan Review Notes
Plan Review Notes For Permit 21070558
Permit Number 21070558
Review Stop P
Sequence Number 2
Notes
Date Text
2021-12-09 13:21:172ND REVIEW FBC-2020 PLUMBING
 PERMIT-21070558
 12/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS 2-8 LISTED BELOW
 WERE NOT ADDRESSED. THE CORRECTED PLANS WERE NOT
 UPLOADED FOR REVIEW.
  
 2) P301, P302, & P601: PROVIDE 3-INCH DRAIN STACKS AND
 BRANCH DRAINS FOR THE WASHING MACHINES (WM-1)- SECTION
 406.2 FBC P. PLEASE NOTE THE A/P601 STACK CONTINUATION
 IS UNDERSIZED.
  
 3) P301 & P601: PROVIDE A FLOOR DRAIN FOR THE ICE
 MACHINE (IM-1) IF REQUIRED BY MANUFACTURER?S
 SPECIFICATIONS (NOT PROVIDED)- SECTION 412.2 FBC P.
  
 4) P301 & P601: SHOW THE LOCATION OF THE REQUIRED
 CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 SEWER- SECTION 708.1.2 FBC P.
  
 5) P401 & P602: SHOW THE LOCATIONS OF THE MAIN WATER
 DISTRIBUTION SHUTOFF VALVES FOR EACH DWELLING UNIT-
 SECTION 606.1 (2) (6) FBC P.
  
 6) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE
 LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON
 THE EXTERIOR OF THE BUILDING- SECTION 502.1 FBC P.
  
 7) P401, P402, P602, P701: THE HWR LINE IS NOT SHOWN IN
 THE WATER HEATER DETAIL- SECTION 607.2 FBC P. PLEASE
 PROVIDE HOT WATER PIPIE INSULATION DETAILS- THICKNESS
 AND R-VALUE- TABLE C403.2.10 FBC EC.
  
 8) P701: THE LOCATION OF THE EXPANSION TANK FOR THE
 TANKLESS WATER HEATER MUST BE IN ACCORDANCE WITH
 MANUFACTURER'S SPECIFICATIONS WHICH HAVE NOT BEEN
 PROVIDED- SECTION 502.1 FBC P. PLEASE NOTE THAT
 EXPANSION TANKS FOR STORAGE TYPE WATER HEATERS SHALL BE
 LOCATED DOWNSTREAM OF ALL CHECK VALVES AND PRESSURE
 REDUCING VALVES- SECTION 607.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  