2021-07-30 11:14:55 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21070558 |
| 7/30/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A1.10 & P000: THE CODE RESEARCH DATA ON A1.10 |
| INDICATES THE USE AND OCCUPANCY OF THE BUILDING TO BE |
| R3 WITH COMPLIANCE UNDER THE FBC RES. 2020, HOWEVER IT |
| IS ALSO INDICATING COMPLIANCE WITH THE FBC |
| ACCESSIBILITY CODE WHICH IS NOT COVERED IN THE |
| RESIDENTIAL CODE. THE PLUMBING COMPLIANCE DATA UNDER |
| NOTE #1 (P000) INDICATES COMPLIANCE WITH THE FBC |
| PLUMBING WHICH IS THE COMMERCIAL CODE. DUE TO THESE |
| CONFLICTS THE FOLLOWING REVIEW WILL BE CONDUCTED WITH |
| THE MOST STRINGENT CODES APPLIED. |
| |
| 2) P301, P302, & P601: PROVIDE 3-INCH DRAIN STACKS AND |
| BRANCH DRAINS FOR THE WASHING MACHINES (WM-1)- SECTION |
| 406.2 FBC P. PLEASE NOTE THE A/P601 STACK CONTINUATION |
| IS UNDERSIZED. |
| |
| 3) P301 & P601: PROVIDE A FLOOR DRAIN FOR THE ICE |
| MACHINE (IM-1) IF REQUIRED BY MANUFACTURER?S |
| SPECIFICATIONS (NOT PROVIDED)- SECTION 412.2 FBC P. |
| |
| 4) P301 & P601: SHOW THE LOCATION OF THE REQUIRED |
| CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND |
| SEWER- SECTION 708.1.2 FBC P. |
| |
| 5) P401 & P602: SHOW THE LOCATIONS OF THE MAIN WATER |
| DISTRIBUTION SHUTOFF VALVES FOR EACH DWELLING UNIT- |
| SECTION 606.1 (2) (6) FBC P. |
| |
| 6) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE |
| LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON |
| THE EXTERIOR OF THE BUILDING- SECTION 502.1 FBC P. |
| |
| 7) P401, P402, P602, P701: THE HWR LINE IS NOT SHOWN IN |
| THE WATER HEATER DETAIL- SECTION 607.2 FBC P. PLEASE |
| PROVIDE HOT WATER PIPIE INSULATION DETAILS- THICKNESS |
| AND R-VALUE- TABLE C403.2.10 FBC EC. |
| |
| 8) P701: THE LOCATION OF THE EXPANSION TANK FOR THE |
| TANKLESS WATER HEATER MUST BE IN ACCORDANCE WITH |
| MANUFACTURER'S SPECIFICATIONS WHICH HAVE NOT BEEN |
| PROVIDED- SECTION 502.1 FBC P. PLEASE NOTE THAT |
| EXPANSION TANKS FOR STORAGE TYPE WATER HEATERS SHALL BE |
| LOCATED DOWNSTREAM OF ALL CHECK VALVES AND PRESSURE |
| REDUCING VALVES- SECTION 607.3 FBC P. |
| |
| 9) P701: PLEASE PROVIDE A SHOWER FLOOR AND LINER |
| DETAIL- SECTION 417.5.2 FBC P. |
| |
| 10) SHEET A-410 ACCESSIBLE PLUMBING FIXTURE DETAILS |
| MISSING PER FBC ACC- |
| A) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE WATER |
| CLOSETS- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE |
| LAVATORIES- SECTION 606.2. |
| C) TURNING SPACE DIAMETER DIMENSION SECTION 304.3. |
| D) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE SHOWER- |
| SECTION 608.2.1 |
| E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE ACCESSIBLE SHOWERS- SECTION 608.3.2. |
| PLEASE SEE FIGURE 608.3.2 AND CORRECT THE DRAWING. |
| F) VERTICAL GRAB BARS ARE NOT IN COMPLIANCE WITH |
| SECTION 609.4 WHICH REQUIRES GRAB BARS TO BE INSTALLED |
| IN HORIZONTAL POSITIONS. |
| G) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| SHOWER- SECTION 608.5.2. WHERE A SEAT IS PROVIDED, THE |
| CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| INSTALLED ON THE BACK WALL ADJACENT TO THE SEAT WALL |
| AND SHALL BE LOCATED 27 INCHES MAXIMUM FROM THE SEAT |
| WALL. |
| H) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. |
| SPECS WERE NOT INCLUDED IN THE FIXTURE SCHEDULE ON |
| P801. |
| I) ACCESSIBLE SHOWER SEAT DETAILS AND FIGURES- SECTIONS |
| 610.3 & 610.3.2. |
| |
| 11) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| 105.1 FBC P. |
| |
| 12) PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1WPB |
| AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |