2021-07-30 12:12:38 | 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21070558 |
| 7/30/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE |
| LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON |
| THE EXTERIOR OF THE BUILDING- SECTIONS 305.1 & 624.1 |
| FBC FG. |
| |
| 2) P401 & P701: SHOW WH CONDENSATE LINES, |
| NEUTRALIZATION DEVICE AND CONDENSATE LINE DISPOSAL |
| LOCATIONS- SECTION 307.2 FBC FG. |
| |
| 3) P401 & P701: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE WATER HEATERS- SECTION 624.1 FBC FG. PROVIDE A |
| BASIC INSTALLATION DIAGRAM ON THE PLAN SHOWING THE |
| REQUIRED CLEARANCES FROM THE UNITS TO GRADE, OVERHEAD |
| CONSTRUCTION AND TO THE ADJACENT WINDOW OPENING- WATER |
| HEATER- SECTIONS 624.1 & 503.8 FBC FG. |
| |
| 4) P601 OR P602: PLEASE PROVIDE A GAS RISER DRAWING- |
| SECTION 107.3.5.1.3 WPB. PLEASE NOTE THE GAS DEMAND |
| SCHEDULE INDICATES 1-INCH PE BRANCHES TO THE WATER |
| HEATERS THAT ARE UNDERSIZED USING THE LONGEST LENGTH |
| METHOD AND THE SPECIFIED SIZING TABLE 402.4(21) FBC FG |
| AND SECTION 402.4.1 FBC FG. GAS RISER: |
| |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| J) PIPE SIZING TABLES. |
| |
| 5) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE |
| GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR |
| FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES. |
| |
| 6) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR |
| INSTALLATION OF THE GENERATOR- SECTION 105.1 & 107.2.1 |
| WPB, HOWEVER, IN ORDER TO PERFORM A COMPLETE GAS REVIEW |
| AT THIS TIME PLEASE SUBMIT A CUT SHEET FOR THE |
| GENERATOR SHOWING THE BTUH LOAD AND INPUT PRESSURE- |
| SECTIONS 305.1 & 402.2 FBC FG. |
| |
| 7) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1 |
| WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |