Plan Review Notes
Plan Review Notes For Permit 21070558
Permit Number 21070558
Review Stop G
Sequence Number 1
Notes
Date Text
2021-07-30 12:12:381ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21070558
 7/30/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE
 LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON
 THE EXTERIOR OF THE BUILDING- SECTIONS 305.1 & 624.1
 FBC FG.
  
 2) P401 & P701: SHOW WH CONDENSATE LINES,
 NEUTRALIZATION DEVICE AND CONDENSATE LINE DISPOSAL
 LOCATIONS- SECTION 307.2 FBC FG.
  
 3) P401 & P701: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE WATER HEATERS- SECTION 624.1 FBC FG. PROVIDE A
 BASIC INSTALLATION DIAGRAM ON THE PLAN SHOWING THE
 REQUIRED CLEARANCES FROM THE UNITS TO GRADE, OVERHEAD
 CONSTRUCTION AND TO THE ADJACENT WINDOW OPENING- WATER
 HEATER- SECTIONS 624.1 & 503.8 FBC FG.
  
 4) P601 OR P602: PLEASE PROVIDE A GAS RISER DRAWING-
 SECTION 107.3.5.1.3 WPB. PLEASE NOTE THE GAS DEMAND
 SCHEDULE INDICATES 1-INCH PE BRANCHES TO THE WATER
 HEATERS THAT ARE UNDERSIZED USING THE LONGEST LENGTH
 METHOD AND THE SPECIFIED SIZING TABLE 402.4(21) FBC FG
 AND SECTION 402.4.1 FBC FG. GAS RISER:
  
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 J) PIPE SIZING TABLES.
  
 5) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE
 GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR
 FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES.
  
 6) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE GENERATOR- SECTION 105.1 & 107.2.1
 WPB, HOWEVER, IN ORDER TO PERFORM A COMPLETE GAS REVIEW
 AT THIS TIME PLEASE SUBMIT A CUT SHEET FOR THE
 GENERATOR SHOWING THE BTUH LOAD AND INPUT PRESSURE-
 SECTIONS 305.1 & 402.2 FBC FG.
  
 7) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  