2021-08-31 14:17:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE ARE INDICATION OF WHAT APPEARS TO BE SHOWER |
| HANDRAILS; HOWEVER, THERE ARE NO DETAILED INDICATIONS |
| OF MEETING THE REQUIRMENTS OF THE FIRE CODE. |
| |
| PER NFPA 101 |
| |
| 32.2.2.7 WHERE BATHTUBS, BATHTUB-SHOWER COMBINATIONS, |
| OR SHOWERS ARE |
| PRESENT, GRAB BARS SHALL BE PROVIDED IN ACCORDANCE WITH |
| THE PROVISIONS |
| OF 24.2.8. |
| |
| 24.2.8.2.1* BATHTUB END WALL VERTICAL GRAB BARS. END |
| WALL VERTICAL |
| GRAB BARS FOR BATHTUBS SHALL COMPLY WITH ALL OF THE |
| FOLLOWING: |
| (1) VERTICAL GRAB BARS SHALL HAVE A LENGTH OF NOT LESS |
| THAN 36 IN. |
| (914 MM). |
| (2) VERTICAL GRAB BARS SHALL BE LOCATED BETWEEN 24 IN. |
| (610 MM) AND |
| 27 IN. (686 MM) ABOVE THE FINISHED FLOOR, MEASURED TO |
| THE LOWER END. |
| (3) VERTICAL GRAB BARS SHALL BE INSTALLED AT THE END |
| THAT IS LEAST OBSTRUCTED |
| FOR ENTRY AND EGRESS. |
| (4) VERTICAL GRAB BARS SHALL BE LOCATED BETWEEN 9 IN. |
| (228 MM) AND |
| 12 IN. (305 MM) FROM THE OPEN ENTRY AND EGRESS SIDE OF |
| THE BATHTUB |
| OR BATHTUB-SHOWER COMBINATION, MEASURED HORIZONTALLY |
| FROM THE |
| EXTERIOR PLANE OF THE BATHTUB OR BATHTUB-SHOWER |
| COMBINATION. |
| |
| PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE. |
| |
| |
| |
| |
| 2) THE PRIMARY MEAND OF ESCAPE FROM THE 2ND FLOOR DOES |
| NOT APPEAR TO MEET THE REQUIREMENTS OF UNENCLOSED ON |
| THE 1ST FLOOR. |
| |
| THE 1ST FLOOR PORTION HAS TO BE A 1/2 HOUR PROTECTED |
| ARE WITHOUT FURNITURE. |
| |
| 32.2.2.4.2 STAIRS SHALL COMPLY WITH 7.2.2.5.3. |
| 32.2.2.4.3 THE ENTIRE PRIMARY MEANS OF ESCAPE SHALL BE |
| ARRANGED SO THAT |
| OCCUPANTS ARE NOT REQUIRED TO PASS THROUGH A PORTION OF |
| A STORY ABOVE OR |
| A STORY BELOW, UNLESS THAT ROUTE IS SEPARATED FROM ALL |
| SPACES ON THAT STORY |
| BY CONSTRUCTION HAVING A MINIMUM 1?2-HOUR FIRE |
| RESISTANCE RATING. |
| 32.2.2.4.4 IN BUILDINGS OF CONSTRUCTION OTHER THAN TYPE |
| II(000), |
| TYPE III(200), OR TYPE V(000), THE SUPPORTING |
| CONSTRUCTION SHALL BE |
| PROTECTED TO AFFORD THE REQUIRED FIRE RESISTANCE RATING |
| OF THE SUPPORTED |
| WALL. |
| 32.2.2.4.5 STAIRS THAT CONNECT A STORY AT STREET LEVEL |
| TO ONLY ONE OTHER |
| STORY SHALL BE PERMITTED TO BE OPEN TO THE STORY THAT |
| IS NOT AT STREET LEVEL. |
| 32.2.2.4.6 IN BUILDINGS THREE OR FEWER STORIES IN |
| HEIGHT AND PROTECTED |
| BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH 32.2.3.5, |
| STAIR ENCLOSURES SHALL NOT BE REQUIRED, PROVIDED THAT |
| THERE STILL REMAINS |
| A PRIMARY MEANS OF ESCAPE FROM EACH SLEEPING AREA THAT |
| DOES NOT REQUIRE |
| OCCUPANTS TO PASS THROUGH A PORTION OF A LOWER FLOOR, |
| UNLESS THAT ROUTE |
| IS SEPARATED FROM ALL SPACES ON THAT FLOOR BY |
| CONSTRUCTION HAVING A MINIMUM |
| 1?2-HOUR FIRE RESISTANCE RATING. |
| 32.2.2.4.7 STAIRS SERVING A MAXIMUM OF TWO STORIES IN |
| BUILDINGS PROTECTED |
| WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH |
| 32.2.3.5 SHALL BE PERMITTED TO BE UNENCLOSED. |
| |
| ONE OF THE REQUIREMENTS OF THIS CODE TO USE AN |
| UNENCLOSED STAIR IS WITH PROMPT EVACUATION CAPABILITY. |
| |
| THE PROVISIONS OF 32/33.2.2.4.7 PERMIT A TWO-STORY OPEN |
| STAIR |
| (AND ITS ASSOCIATED EXPOSURE TO THE AREAS THAT ARE |
| OCCUPIED OR FURNISHED, |
| OR BOTH, ON THE GROUND FLOOR) TO SERVE AS PRIMARY MEANS |
| OF |
| ESCAPE FOR NEW SMALL FACILITIES AND EXISTING SMALL |
| FACILITIES (NOT |
| MORE THAN EIGHT RESIDENTS) WITH PROMPT EVACUATION |
| CAPABILITY, |
| PROVIDED THAT THE FACILITY IS SPRINKLERED USING |
| QUICK-RESPONSE OR |
| RESIDENTIAL SPRINKLERS. |
| |
| 32.1.5 ACCEPTABILITY OF MEANS OF EGRESS OR ESCAPE. NO |
| MEANS OF |
| ESCAPE OR MEANS OF EGRESS SHALL BE CONSIDERED AS |
| COMPLYING WITH THE |
| MINIMUM CRITERIA FOR ACCEPTANCE, UNLESS EMERGENCY |
| EVACUATION DRILLS |
| ARE REGULARLY CONDUCTED USING THAT ROUTE IN ACCORDANCE |
| WITH THE REQUIREMENTS |
| OF 32.7.3 |
| |
| 3.3.81.2 PROMPT EVACUATION CAPABILITY. THE ABILITY OF A |
| GROUP TO |
| MOVE RELIABLY TO A POINT OF SAFETY IN A TIMELY MANNER |
| THAT IS EQUIVALENT |
| TO THE CAPACITY OF A HOUSEHOLD IN THE GENERAL |
| POPULATION. |
| |
| A.3.3.81 EVACUATION CAPABILITY. THE EVACUATION |
| CAPABILITY OF THE |
| RESIDENTS AND STAFF IS A FUNCTION OF BOTH THE ABILITY |
| OF THE RESIDENTS TO |
| EVACUATE AND THE ASSISTANCE PROVIDED BY THE STAFF. IT |
| IS INTENDED THAT THE |
| EVACUATION CAPABILITY BE DETERMINED BY THE PROCEDURE |
| ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. IT IS ALSO INTENDED THAT |
| THE TIMING OF DRILLS, |
| THE RATING OF RESIDENTS, AND SIMILAR ACTIONS RELATED TO |
| DETERMINING THE |
| EVACUATION CAPABILITY BE PERFORMED BY PERSONS APPROVED |
| BY OR ACCEPTABLE |
| TO THE AUTHORITY HAVING JURISDICTION. THE EVACUATION |
| CAPABILITY CAN |
| BE DETERMINED BY THE USE OF THE DEFINITIONS IN 3.3.81, |
| THE APPLICATION OF |
| NFPA 101A CHAPTER 6, OR A PROGRAM OF DRILLS (TIMED). |
| EVACUATION DOES NOT INCLUDE THE RELOCATION OF OCCUPANTS |
| WITHIN A |
| BUILDING. |
| WHERE DRILLS ARE USED IN DETERMINING EVACUATION |
| CAPABILITY, IT IS |
| SUGGESTED THAT THE FACILITY CONDUCT AND RECORD FIRE |
| DRILLS SIX TIMES PER |
| YEAR ON A BIMONTHLY BASIS, WITH A MINIMUM OF TWO DRILLS |
| CONDUCTED |
| DURING THE NIGHT WHEN RESIDENTS ARE SLEEPING, AND THAT |
| THE FACILITY CONDUCT |
| THE DRILLS IN CONSULTATION WITH THE AUTHORITY HAVING |
| JURISDICTION. RECORDS |
| SHOULD INDICATE THE TIME TAKEN TO REACH A POINT OF |
| SAFETY, DATE AND TIME |
| OF DAY, LOCATION OF SIMULATED FIRE ORIGIN, ESCAPE PATHS |
| USED, AND COMMENTS |
| RELATING TO RESIDENTS WHO RESISTED OR FAILED TO |
| PARTICIPATE IN THE |
| DRILLS. |
| TRANSLATION OF DRILL TIMES TO EVACUATION CAPABILITY IS |
| DETERMINED AS |
| FOLLOWS: |
| (1) 3 MINUTES OR LESS ? PROMPT |
| (2) OVER 3 MINUTES, BUT NOT IN EXCESS OF 13 MINUTES ? |
| SLOW |
| (3) MORE THAN 13 MINUTES ? IMPRACTICAL |
| EVACUATION CAPABILITY, IN ALL CASES, IS BASED ON THE |
| TIME OF DAY OR |
| NIGHT WHEN EVACUATION OF THE FACILITY WOULD BE MOST |
| DIFFICULT, SUCH AS |
| WHEN RESIDENTS ARE SLEEPING OR FEWER STAFF ARE PRESENT. |
| EVACUATION CAPABILITY DETERMINATION IS CONSIDERED SLOW |
| IF THE FOLLOWING |
| CONDITIONS ARE MET: |
| (1) ALL RESIDENTS ARE ABLE TO TRAVEL TO CENTRALIZED |
| DINING FACILITIES WITHOUT |
| CONTINUOUS STAFF ASSISTANCE. |
| (2) THERE IS CONTINUOUS STAFFING WHENEVER THERE ARE |
| RESIDENTS IN THE |
| FACILITY. |
| |
| IT WOULD BE ANTICIPATED THAT THE EVACUATION TIME OF 3 |
| MINUTES WOULD BE FOR CLIENTS WITH NO OR LIMITED |
| PHYISCAL/MENTAL DISABILITES. |
| |
| PLEASE REVIEW AND PROVIDE DETAILS OF THE PROPOSED |
| CLIENTS AND THE ABILITY TO MEET THE PROMPT EVACUATION |
| OR CORRECT AND ENLCOSE THE STAIT EITHER AT THE TOP OR |
| THE BOTTOM. |
| |
| |
| |
| |
| 3) THERE ARE 2 EXTERIOR DOORS/GATES WITHIN THE EGRESS |
| TRAVEL PATH LEADING TO A PUBLIC WAY OR POINT OF SAFETY. |
| |
| 32.2.2.5.5 NO DOOR IN ANY MEANS OF ESCAPE, OTHER THAN |
| THOSE MEETING |
| THE REQUIREMENT OF 32.2.2.5.5.1, 32.2.2.5.5.2, OR |
| 32.2.2.5.5.3, SHALL BE |
| LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. |
| |
| PLEASE PROVIDE DETAILS INDICATING HOW THESE DOORS/GATES |
| WILL COMPLY WITH THE CODE. |
| |
| |
| |
| 4) THERE ARE INDICATIONS OF A 13D FIRE SPRINKLER |
| SYSTEM; HOWEVER, THERE IS ONLY 1 DOMESTIC WATER LINE |
| INDICATED. |
| |
| PER THE WATER UTILITIES DEPARTMENT, A DEDICATED WATER |
| SUPPLY AND WATER METER FOR A FIRE SPRINKLER SYSTEM IS |
| REQUIRED. |
| |
| PLEASE CONTACT THE WATER UTILITIES DEPARTMENT FOR THEIR |
| REQUIERMENTS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| AND PROVIDE REVISION AS AND WHERE REQUIRED PRIOR TO |
| INSTALLATIONS. |
| |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |