Plan Review Notes
Plan Review Notes For Permit 21070558
Permit Number 21070558
Review Stop B
Sequence Number 1
Notes
Date Text
2021-09-01 10:56:56NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB
 CHAPTER 1 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING A-1.10 SHOWS R3 "CONGREGATE" LIVING FACILITY
 WITH 5 OCCUPANTS MAXIMUM - DRAWING STATES COMPLIANCE IS
 PER FBC RESIDENTIAL CODE - FBC R310.5.1 ALLOWS "CARE"
 FACILITIES (NOT "CONGREGATE" FACILITIES) WITHIN A
 DWELLING. CARE FACILITIES FOR FIVE OR FEWER PERSONS
 RECEIVING CARE THAT ARE WITHIN A SINGLE-FAMILY DWELLING
 ARE PERMITTED TO COMPLY WITH THE FLORIDA BUILDING CODE,
 // R3 CONGREGATE WILL NEED TO USE THE FBC BUILDING.
 2) PLEASE SHOW DESCRIPTION AS (CONGREGATE (TRANSIENT)
 OR (NON TRANSIENT) ) PER FBC 310.5
 3) PLEASE PROVIDE COMPLETE PRODUCT APPROVALS FOR THE
 EXTERIOR WINDOWS, DOORS, ROOFING SYSTEMS ETC.. ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED BY PRODUCT APPROVAL NUMBER ON THE DRAWINGS. FBC
 WPB 107.2.1
 4) HARDI PLANK SIDING IS SUBJECT TO WIND LOADS - PLEASE
 PROVIDE ATTACHMENT DETAILS OR PRODUCT APPROVALS TO
 COMPLY WITH FBC R703.1.2
 5) PLEASE SHOW THE WOOD EXTERIOR WALLS -WATER RESISTIVE
 BARRIER TO COMPLY WITH FBC R703.2
  
 DRAWINGS WERE REVIEWED BASED ON THE FBC RESIDENTIAL -
 IF CORRECTIONS SUGGEST DESIGN TO BE PER FBC BUILDING
 ADDITIONAL CORRECTIONS MAY BE REQUIRED.
  
  