2021-10-18 10:11:55 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21070557 |
| 10/18/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P1: PLEASE PROVIDE WATER HEATER EQUIPMENT |
| SCHEDULES ON THE PLAN AND SUBMIT MANUFACTURERS |
| SPECIFICATIONS. INDICATE THE MAKES AND MODELS, GALLON |
| SIZES, AND EFFICIENCY RATINGS, AND INCLUDE THE |
| COMPLIANCE DATA IN THE ENERGY CALCULATIONS- TABLE |
| C404.2 FBC EC. |
| |
| 2) WPB CROSS CONNECTION MANUAL: PLEASE ITEM C. CONTROL |
| OF BACKFLOW. A BACKFLOW PREVENTER IS REQUIRED FOR A |
| MULTI-FAMILY RESIDENTIAL AT THE POINT OF POTABLE WATER |
| SERVICE DELIVERY. |
| |
| PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |