Plan Review Notes
Plan Review Notes For Permit 21070509
Permit Number 21070509
Review Stop P-GREASE
Sequence Number 1
Notes
Date Text
2021-08-02 11:09:031) ) SHT. P-102 - LEFT SIDE OF DRAWING - THERE IS A
 NOTE STATING " EX. GW FROM TENANTS" BUT THIS GREASE
 LINE IS SHOWN CONNECTED TO THE SANITARY SYSTEM. THE
 GREASE CANNOT CONNECT TO THE SANITARY SYSTEM.
 FBC-PLUMBING SEC.1003.1.
 2) ALL HAND SINKS SHALL DISCHARGE TO THE SANITARY
 SYSTEM, NOT TO THE GREASE WASTE SYSTEM PER FBC-PLUMBING
 SEC.1003.2.
 3) SUBMIT GREASE TRAP SIZING CALCULATIONS TO ENSURE
 THAT THE EXISTING TRAPS HAVE THE REQUIRED CAPACITY FOR
 THE NEW GREASE WASTE SYSTEM LOAD. FBC-PLUMBING
 SECS.1003.2, 1003.3.5.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW