Plan Review Notes For Permit 21070509 |
Permit Number |
21070509 |
|
Review Stop |
P-GREASE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-08-02 11:09:03 | 1) ) SHT. P-102 - LEFT SIDE OF DRAWING - THERE IS A | | NOTE STATING " EX. GW FROM TENANTS" BUT THIS GREASE | | LINE IS SHOWN CONNECTED TO THE SANITARY SYSTEM. THE | | GREASE CANNOT CONNECT TO THE SANITARY SYSTEM. | | FBC-PLUMBING SEC.1003.1. | | 2) ALL HAND SINKS SHALL DISCHARGE TO THE SANITARY | | SYSTEM, NOT TO THE GREASE WASTE SYSTEM PER FBC-PLUMBING | | SEC.1003.2. | | 3) SUBMIT GREASE TRAP SIZING CALCULATIONS TO ENSURE | | THAT THE EXISTING TRAPS HAVE THE REQUIRED CAPACITY FOR | | THE NEW GREASE WASTE SYSTEM LOAD. FBC-PLUMBING | | SECS.1003.2, 1003.3.5.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|