2021-08-11 10:41:26 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21070509 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE |
| HOODS SHALL HAVE A SEPARATE PERMIT , DRAWINGS AND PLAN |
| REVIEW AS THEY WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| |
| 2) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE |
| REFRIGERATION SYSTEMS SHALL HAVE A SEPARATE PERMIT, |
| DRAWINGS AND PLAN REVIEW AS THEY WILL NOT BE REVIEWED |
| UNDER THIS PERMIT. |
| |
| 3) SHEET M-001: PLEASE REVISIT THE OUTDOOR AIR |
| CALCULATIONS. USING THE NUMBERS YOU SHOW IN THE MINIMUM |
| VENTILATION RATES IN BREATHING ZONE TABLE, I CALCULATE |
| A TOTAL OF 1,765 CFM REQUIRED OUTDOOR AIR FOR THIS |
| TENANT SPACE. |
| |
| 4) SHEET M-103: PLEASE SHOW THE CONDENSATE PIPING, |
| MATERIAL AND THE TERMINATION LOCATION. FBC M 307 |
| |
| 5) SHEET M-103: PLEASE PROVIDE A DETAIL DRAWING OF THE |
| BOILER EQUIPMENT EXHAUST. PROVIDE MATERIAL TYPE AND |
| LENGTHS OF PIPING ALONG WITH COMPLIANCE OF FBC M |
| CHAPTER 10. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |