2021-08-11 14:36:26ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-106
  
 1) RISER DIAGRAM SHOWS FEEDER FROM MDP TO EMH AS 3/0
 PROTECTED BY A 225 AMPERE BREAKER?
  
 2) GENERATOR REQUIRES A SEAPARATE PERMIT AND PLANS.
  
 PAGE E-102A
  
 KITCHEN, PREP AREAS, INDOOR WET LOCATIONS, AND WITHIN
 6' OF A SINK ALL THESE AREAS REQUIRE GFCI PROTECTION
 PER 210.8(B)
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100
 AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS
 SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 (2) KITCHENS
 (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8
 M (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF THE
 SINK
 (6) INDOOR WET LOCATIONS