Date |
Text |
2021-07-16 19:25:23 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21070494 |
| 7/16/2021 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| 1- I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND |
| THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF |
| ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A |
| PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL |
| CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC. |
| 105.1. |
| 2- SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES |
| SECS. G2413.4.1, G2413.4.2. |
| 3- SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4- TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 5- SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. |
| 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| 6- LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC FUEL GAS |
| SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| THROUGH 402.4 (37) OR 2020 FBC FUEL GAS RES. SEC. |
| G2413. |
| 7- SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR |
| 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| 8- SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM 2020 FBC FUEL GAS SEC. 402.3 OR 2020 FBC FUEL |
| GAS RES. SEC. G2413.3 |
| 9- SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2020 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 10- SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| APPLIANCE. COMPLY WITH 2020 FBC FUEL GAS SEC. TABLE |
| 402.4 (28) OR 2020 FBC FUEL GAS RES. SEC. TABLE G2413.4 |
| (12) FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| 11- WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6695 |
| |