Plan Review Notes
Plan Review Notes For Permit 21070354
Permit Number 21070354
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-02 10:33:21JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R8 SELECTED OPTION FOR SYSTEM NO W-1
 EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (170). ZONE 3 IS MARKED ?N/A? WHICH
 INDICATES SYSTEM IS ?NOT APPLICABLE? TO ZONE1 PRIME
 DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED. PLEASE
 PROVIDE 2020 CODE VERSION PRODUCT APPROVAL/NOA THAT
 MEETS OR EXCEEDS DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE D AREAS. SIGNED AND SEALED NAILING
 CALCULATIONS MAY BE REQUIRED. YOU MAY WANT TO CONSIDER
 USING FL16709-R8 SYSTEM W-3.
  