Plan Review Notes
Plan Review Notes For Permit 21070330
Permit Number 21070330
Review Stop E
Sequence Number 1
Notes
Date Text
2021-07-26 07:24:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN, PLEASE SUBMIT A LAYOUT OF THE
 ELECTRIC IN THE SIGN AND TO THE SIGN.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved