Date |
Text |
2021-07-30 11:25:31 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL16709-R8 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-4 TO |
| INCLUDE LIMITATIONS PAGE(S). |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R8 SELECTED SYSTEM NO W-1; EXPOSURE |
| (B); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H < 15); |
| ULTIMATE WIND SPEED 180 IS NOT CORRECT. THE CORRECT |
| EXPOSURE CATEGORY FOR THE LISTED ADDRESS IS EXPOSURE C. |
| PLEASE PROVIDE THE CORRECT OPTIONS. |
| 3. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE METAL TO BE USED. |
| 4. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE TILE ADHESIVE TO BE USED. |
| 5. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| ROOF HEIGHT. |
| |