Date |
Text |
2022-05-16 08:01:42 | 3RD REVIEW FMC |
| PERMIT: 21070278 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| IF USING AN ALTERNATE MEANS TO MEET THE OUTDOOR AIR |
| REQUIREMENT PLEASE SUBMIT A COMPLETE DESIGN. FMC 403.2 |
| OUTDOOR AIR REQUIRED. THE MINIMUM OUTDOOR AIRFLOW RATE |
| SHALL BE DETERMINED IN ACCORDANCE WITH SECTION 403.3. |
| |
| EXCEPTION: WHERE THE REGISTERED DESIGN PROFESSIONAL |
| DEMONSTRATES THAT AN ENGINEERED VENTILATION SYSTEM |
| DESIGN WILL PREVENT THE MAXIMUM CONCENTRATION OF |
| CONTAMINANTS FROM EXCEEDING THAT OBTAINABLE BY THE RATE |
| OF OUTDOOR AIR VENTILATION DETERMINED IN ACCORDANCE |
| WITH SECTION 403.3, THE MINIMUM REQUIRED RATE OF |
| OUTDOOR AIR SHALL BE REDUCED IN ACCORDANCE WITH SUCH |
| ENGINEERED SYSTEM DESIGN. |
| |
| 1) SHEET M-13: EACH CONTAMINANT OF CONCERN, FOR |
| PURPOSES OF THE DESIGN, SHALL BE IDENTIFIED. FOR EACH |
| CONTAMINANT OF CONCERN, INDOOR SOURCES AND OUTDOOR |
| SOURCES SHALL BE IDENTIFIED, AND EMISSION RATE FOR EACH |
| CONTAMINANT OF CONCERN FROM EACH SOURCE SHALL BE |
| DETERMINED. PLEASE SHOW THIS INFORMATION IN THE CHART |
| SUBMITTED. ASHRAE 62.1-2016 |
| |
| 2) SHEET M-13: THERE ARE SEVERAL DIFFERENT TUBE SIZES |
| FOR THE MATTERHORN 1000, PLEASE IDENTIFY THE TUBE SIZE |
| IN THE CHART FOR THIS DESIGN. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |