Plan Review Notes For Permit 21070278
Permit Number 21070278
Review Stop M
Sequence Number 3
Notes
Date Text
2022-05-16 08:01:423RD REVIEW FMC
 PERMIT: 21070278
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 IF USING AN ALTERNATE MEANS TO MEET THE OUTDOOR AIR
 REQUIREMENT PLEASE SUBMIT A COMPLETE DESIGN. FMC 403.2
 OUTDOOR AIR REQUIRED. THE MINIMUM OUTDOOR AIRFLOW RATE
 SHALL BE DETERMINED IN ACCORDANCE WITH SECTION 403.3.
  
 EXCEPTION: WHERE THE REGISTERED DESIGN PROFESSIONAL
 DEMONSTRATES THAT AN ENGINEERED VENTILATION SYSTEM
 DESIGN WILL PREVENT THE MAXIMUM CONCENTRATION OF
 CONTAMINANTS FROM EXCEEDING THAT OBTAINABLE BY THE RATE
 OF OUTDOOR AIR VENTILATION DETERMINED IN ACCORDANCE
 WITH SECTION 403.3, THE MINIMUM REQUIRED RATE OF
 OUTDOOR AIR SHALL BE REDUCED IN ACCORDANCE WITH SUCH
 ENGINEERED SYSTEM DESIGN.
  
 1) SHEET M-13: EACH CONTAMINANT OF CONCERN, FOR
 PURPOSES OF THE DESIGN, SHALL BE IDENTIFIED. FOR EACH
 CONTAMINANT OF CONCERN, INDOOR SOURCES AND OUTDOOR
 SOURCES SHALL BE IDENTIFIED, AND EMISSION RATE FOR EACH
 CONTAMINANT OF CONCERN FROM EACH SOURCE SHALL BE
 DETERMINED. PLEASE SHOW THIS INFORMATION IN THE CHART
 SUBMITTED. ASHRAE 62.1-2016
  
 2) SHEET M-13: THERE ARE SEVERAL DIFFERENT TUBE SIZES
 FOR THE MATTERHORN 1000, PLEASE IDENTIFY THE TUBE SIZE
 IN THE CHART FOR THIS DESIGN. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  