2022-02-25 09:19:49 | 2ND REVIEW FBC-2020 MECHANICAL |
| PERMIT-21070278 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SEE COMMENTS BELOW FROM THE 1ST REVIEW CYCLE: |
| |
| 2) SHEET M-3: PLEASE SHOW THE OUTDOOR AIR CALCULATIONS |
| FOR EACH USE OF SPACE IN THIS TENANT SPACE. PLEASE |
| REMEMBER YOU MAY USE FOOTNOTE (A) (NET OCCUPIABLE FLOOR |
| AREA) THE KITCHEN, OFFICE AND DINING/BAR ARE SHOWING |
| SMALLER AMOUNTS OF OUTDOOR AIR THAN IS REQUIRED. FBC M |
| 403.3.1.1 AND TABLE 403.3.1.1 THE BAR AND DINING ROOM |
| AREA SHOULD BE CALCULATED AT THEIR OCCUPANCY |
| CLASSIFICATION RATE FROM TABLE 403.3.1.1. TYPICALLY THE |
| BAR IS CALCULATED TO 5 FEET OUT FROM THE BAR. SEE THE |
| 2ND SENTENCE OF SECTION 403.3.1.1 BELOW: |
| |
| THE OCCUPANT LOAD UTILIZED FOR DESIGN OF THE |
| VENTILATION SYSTEM SHALL BE NOT LESS THAN THE NUMBER |
| DETERMINED |
| FROM THE ESTIMATED MAXIMUM OCCUPANT LOAD RATE INDICATED |
| IN TABLE 403.3.1.1. VENTILATION RATES FOR OCCUPANCIES |
| NOT REPRESENTED IN TABLE 403.3.1.1 SHALL BE THOSE FOR A |
| LISTED OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN |
| TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING |
| CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED |
| ENGINEERING ANALYSIS. |
| |
| 6) SHEET M-1: PLEASE SHOW THE CONDENSATION PIPING AND |
| THE TERMINATION LOCATION FOR THE AHU?S. FBC M 307 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |