Plan Review Notes
Plan Review Notes For Permit 21070278
Permit Number 21070278
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-06 06:57:291) SHT. CVR - SHT. #A-403 IS NOT LISTED IN THE INDEX OF
 DRAWINGS. PLEASE INCLUDE.
 2) BASED ON THE OCCUPANT LOAD LISTED ON SHT. A-202, A
 MINIMUM OF TWO WATER CLOSETS ARE REQUIRED FOR THE MALES
 AND TWO FOR THE FEMALES PER FBC-PLUMBING SEC. 403.1 AND
 TABLE 403.1.
 3) SHT. A-403 - MOUNTING HEIGHTS FOR ACCESSIBILITY -
 THE PLAN REFERS TO THE 2014 FBC. THE 2020 EDITION OF
 THE CODE IS IN EFFECT. PLEASE REVISE THIS NOTE.
 4) SHT. A-403 - WATER CLOSET REAR GRAB BAR. THE LAYOUT
 OFF THE REAR GRAB BAR SHALL COMPLY WITH FBC-ACCESS.
 SEC.604.5.2 AND FIGURE 604.5.2.
 5) THE NAMING CONVENTIONS OF THE UPLOADED PLANS DOES
 NOT CORRELATE WITH THE DESCRIPTION OF THE PLANS ON THE
 COVER SHEET. CLARIFY.
 6) INDICATE THE WALL FINISH FOR THE MOP SINK ON THE
 FINISH SCHEDULE. THE WALL FINISH SHALL COMPLY WITH FBC
 -BUILDING SEC. 1210.2.2. EPOXY PAINT ON DRYWALL DOES
 NOT MEET THE INTENT OF THE CODE.
 7) SHT. A-403 - THE CIRCULAR TURNING SPACE IN THE
 TOILET ROOMS APPEARS TO HITTING THE WATER
 CLOSETS.CLARIFY.
 8) A SECTION OF THE BAR SHALL COMPLY WITH
 FBC-ACCESS.902.1, 902.2 & 902.3.
 9) SUBMIT SIZING CALCULATIONS AND THE CAPACITY OF THE
 GREASE INTERCEPTOR. SIZING CALCULATIONS WERE NEVER DONE
 UNDER THE GREASE INTERCEPTOR PERMIT #19110598 AND WERE
 DEFERRED TO THE BUILDOUT. PROVIDE THE MAKE AND MODEL OF
 THE INTERCEPTOR ON THE PLANS. FBC-PLUMBING SEC. 1003.2.
 10) SHT. M-4 - DETAIL #J - THE PVC PIPE ON THE ROOF
 SHALL BE PRROTECTED AGAINST UV RAYS.FBC-PLUMBING
 SEC.303.2
 11) THE HAND SINKS AND DUMP SINK SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER FBC-PLUMBING SEC.1003.2.
 12) THE CLEAR WATER WASTE FROM EVAPORATORS, ICE
 MACHINES, EETC. SHALL NOT DISCHARGE TO THE GREASE WASTE
 SUSTEMS PER FBC=PLUMBING SEC.1003.2.
 13) SHT.P-3 - SIZE ALL THE VENTS ON THE SANITARY RISER
 DIAGRAM. WPB AMEND. TO FBC SECS. 107.2.1, 107.3.5.1.3.
 14) SHT.P-4 - PLUMBING FIXTURE LIST - IN-LINE BACKFLOW
 DEVICES - THE TABLE LISTS 1022 APPROVED BACKFLOW
 DEVICES. THESE BACKFLOWS ARE ONLY APPROVED FOR
 CARBONATED BEVERAGE MACHINES. BACKFLOWW DEVICES FOR
 NON-CARBONATED MACHINES/DISPENSERS SHALL COMPLY WITH
 ASSE 1024. PLACE THIS NOTE ON THE PLANS.WPB AMEND. TO
 FBC SEC. 107.2.1.
 15) A BACKFLOW DEVICE IS REQUIRED ON THE DISHWASHER PER
 FBC-PLUMBING SEC.608.2.
 16) HEATED - WATER CIRCULATION SYSTEMS SHALL BE
 PROVIDED WITH A CIRCULATION PUMP PER FBC-ENERGY
 SEC.C404.6.1.THE PUMP INSTALLATION AND CONTROLS SHALL
 COMPLY WITH FBC-ENERGY SEC. C404.6.1.
 17) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 KHS FLOW SPLITTERS. WPB AMEND. TO FBC SEC. 107.2.1.
 18) SUBMIT DETAILS FOR THE BEER STORAGE AREA. WILL
 THERE BE ANY ADDITIONAL PIPING OTHER THAN THE KEG
 TUBING SEVING THE PRODUCT?
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW