2021-08-16 17:30:15 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21070278 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1 PLEASE SHOW HOW YOU WILL SUPPLY OUTDOOR |
| AIR TO THE AHU UNITS. |
| |
| 2) SHEET M-3: PLEASE SHOW THE OUT AIR CALCULATIONS FOR |
| EACH USE OF SPACE IN THIS TENANT SPACE. PLEASE REMEMBER |
| YOU MAY USE FOOTNOTE (A) (NET OCCUPIABLE FLOOR AREA) |
| THE KITCHEN, OFFICE AND DINING/BAR ARE SHOWING SMALLER |
| AMOUNTS OF OUTDOOR AIR THAN IS REQUIRED. FBC M |
| 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 3) PLEASE SHOW THE ELEVATION OF THE CONDENSING UNITS. |
| WPB ADMINISTRATIVE CODE 107.3.5.1.1 |
| |
| 4) SHEET M-3: PLEASE SHOW THAT THE OUTDOOR AIR FROM |
| KSF-1 IS TEMPERED AIR OR MEETS FBC M 508.1.1 |
| |
| 5) SHEET M-1: PLEASE SHOW THAT THE CONDENSING UNITS ARE |
| PROTECTED FROM DAMAGE. FBC M 303.4 |
| |
| 6) SHEET M-1: PLEASE SHOW THE CONDENSATION PIPING AND |
| THE TERMINATION LOCATION FOR THE AHU?S. FBC M 307 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |