Plan Review Notes
Plan Review Notes For Permit 21070278
Permit Number 21070278
Review Stop G
Sequence Number 1
Notes
Date Text
2021-08-06 14:39:211) SUBMIT COPIES OF THE MANUFACTURER?S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC- FUEL GAS CODE SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FBC-FUEL GAS
 CODE SEC.305.1.
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. FBC-FUEL GAS SEC. 304.1. WHERE COMBUSTION
 AIR IS PROVIDED BY THE BUILDING'S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3.
 3) SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER FBC-FUEL GAS
 SECS. 502 THRU 505.
 4) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. NFPA
 96-14. SECS. 10.4.1, 10.4.3, 10.4.4, 10.5.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  