2021-07-09 10:42:55 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. SUBMITTED PRODUCT APPROVAL FL16709-R7 HAS BEEN |
| REVISED TO FL16709-R8. PLEASE PROVIDE A COMPLETE SET. |
| INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R7 SELECTED OPTION FOR SYSTEM NO W-4; |
| EXPOSURE (C); ENCLOSURE (OPEN); ROOF HEIGHT (H<15); |
| ULTIMATE WIND SPEED (180), IS NOT CORRECT. THE CORRECT |
| EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D. |
| |