2021-08-11 09:59:28 | 1) SHT. S-1 CALLS OUT THIS OCUPANCY AS MERCANTILE "B". |
| THERE IS NO SUCH OCCUPANCY CLASSIFICATION IN THE |
| BUILDING CODE. THIS SPACE WAS PREVIOUSLY CLASIFIED AS |
| AN A-2 OCCCUPANCY ACORDING TO CITY RECORDS. SEC. |
| 303.1.1 OF THE FBC-BUILDING STATES A BUILDING OR TENANT |
| SPACE USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD |
| OF LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS A GROUP |
| "B" OCUPANCY.CLARIFY. |
| 2) SHT. S-1 HAS THE OCUPANT LOAD OF THIS SPACE AS 32 |
| PERSONS. IF THIS OCCUPANT LOAD IS CORRECT, THEN TWO |
| SEPARATE TOILET ROOMS ARE REQUIRED PER |
| FBC-PLUMBING-TABLE 403.1 AND SEC. 403.2. |
| 3) THE DOOR TO THE ACCESSIBLE TOILET ROOM CANNOT SWING |
| INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.FBC-ACCESS. |
| SEC.603.2.3. (SEE EXCEPTION #2). THE PREVIOUS PLANS ON |
| FILE SHOW THE DOOR WINGING OUT.CLARIFY. |
| 4) SHOW THE FIXTURE CLEARANCES OF THE TOILET FIXTURES |
| ON THE FLOOR PLAN FOR THE TOILET ROOM. COMPLY WITH |
| FBC-ACCESS. SEC.604.2, FBC-PLUMBING SEC.405.3.1. |
| 5) THE WALL FINISH AROUND THE MOP SINK SHALL COMPLY |
| WITH FBC-BUILDING SEC. 1210.2.2. |
| 6) SHT. S-1 -SHOW THE REQUIRED CLEAR FLOOR SPACES FOR |
| THE HANDICAPPED ACCESSIBLE PLUMBING FIXTURES ON THE |
| PLAN AND SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACES |
| ON THE PLANS. COMPLY WITH FBC - ACCESS. SECS.604.3..1, |
| 606.2. |
| 7) THE HEIGHT OF THE SERVICE COUNTER SHALL COMPLY WITH |
| FBC-ACCESS. SEC.904.4.1. |
| 8) INDICATE ON THE PLAN IF THERE WILL BE ANY SEATING AT |
| THE EXTERIOR PATIO AREA AND COVERED WALWAY ASSOCIATED |
| WITH THIS BUSINESS. IF SO, THE OCCUPANT LOAD MUST BE |
| INCLUDED IN THE TOTAL OCCUPANT LOAD. FBC-PLUMBING SEC. |
| 403.1. |
| 9) A DRINKING FOUNTAIN IS REQUIRED PER FBC-PLUMBING |
| SEC.410.3 AND TABLE 403.1. A MINIMUM OF 2 DRINKING |
| FOUNTAINS ARE REQUIRED. FBC-ACCESS. SEC.211.1, |
| 10) SHT. S-1 - OCUPANCY CLASSIFICATION NOTE REFERS O |
| THE 2010 EDITION OF THE FBC. THE 2020 CODE IS IN |
| EFFECT. |
| 11) THE EXISTING PLANS FOR THIS SPACE ON FILE WITH THE |
| CITY SHOW THE GREASE INTERCEPTOR AS A 100 GPM UNIT BUT |
| THE EQUIPMENT SCHEDULE ON SHT. S-2 SHOWS THE GREASE |
| INTERCCEPTOR AS 1250 GALLONS. CLARIFY. |
| 12) INDIATE THE CLASSIFICATION OF WORK ON THE PLANS PER |
| FBC-EXISTING BUILDING SEC.601.1. ALSO, INDICATE THE |
| COMPLIANCE METHOD PER FBC-EXISTING SEC.301.3. |
| 13) IT APPEARS THAT A HAND SINK HAS BEEN REMOVED AND |
| THE SERVICE SINK RELOCATED BASED ON PLANS FROM THE |
| PREVIOUS OCCUPANCY. SUBMIT A WATER AND SANITARY RISER |
| DIAGRAM TO SHOW THE CHANGES TO THE SANITARY SYSTEM. |
| |