2021-08-11 09:59:281) SHT. S-1 CALLS OUT THIS OCUPANCY AS MERCANTILE "B".
 THERE IS NO SUCH OCCUPANCY CLASSIFICATION IN THE
 BUILDING CODE. THIS SPACE WAS PREVIOUSLY CLASIFIED AS
 AN A-2 OCCCUPANCY ACORDING TO CITY RECORDS. SEC.
 303.1.1 OF THE FBC-BUILDING STATES A BUILDING OR TENANT
 SPACE USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD
 OF LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS A GROUP
 "B" OCUPANCY.CLARIFY.
 2) SHT. S-1 HAS THE OCUPANT LOAD OF THIS SPACE AS 32
 PERSONS. IF THIS OCCUPANT LOAD IS CORRECT, THEN TWO
 SEPARATE TOILET ROOMS ARE REQUIRED PER
 FBC-PLUMBING-TABLE 403.1 AND SEC. 403.2.
 3) THE DOOR TO THE ACCESSIBLE TOILET ROOM CANNOT SWING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.FBC-ACCESS.
 SEC.603.2.3. (SEE EXCEPTION #2). THE PREVIOUS PLANS ON
 FILE SHOW THE DOOR WINGING OUT.CLARIFY.
 4) SHOW THE FIXTURE CLEARANCES OF THE TOILET FIXTURES
 ON THE FLOOR PLAN FOR THE TOILET ROOM. COMPLY WITH
 FBC-ACCESS. SEC.604.2, FBC-PLUMBING SEC.405.3.1.
 5) THE WALL FINISH AROUND THE MOP SINK SHALL COMPLY
 WITH FBC-BUILDING SEC. 1210.2.2.
 6) SHT. S-1 -SHOW THE REQUIRED CLEAR FLOOR SPACES FOR
 THE HANDICAPPED ACCESSIBLE PLUMBING FIXTURES ON THE
 PLAN AND SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACES
 ON THE PLANS. COMPLY WITH FBC - ACCESS. SECS.604.3..1,
 606.2.
 7) THE HEIGHT OF THE SERVICE COUNTER SHALL COMPLY WITH
 FBC-ACCESS. SEC.904.4.1.
 8) INDICATE ON THE PLAN IF THERE WILL BE ANY SEATING AT
 THE EXTERIOR PATIO AREA AND COVERED WALWAY ASSOCIATED
 WITH THIS BUSINESS. IF SO, THE OCCUPANT LOAD MUST BE
 INCLUDED IN THE TOTAL OCCUPANT LOAD. FBC-PLUMBING SEC.
 403.1.
 9) A DRINKING FOUNTAIN IS REQUIRED PER FBC-PLUMBING
 SEC.410.3 AND TABLE 403.1. A MINIMUM OF 2 DRINKING
 FOUNTAINS ARE REQUIRED. FBC-ACCESS. SEC.211.1,
 10) SHT. S-1 - OCUPANCY CLASSIFICATION NOTE REFERS O
 THE 2010 EDITION OF THE FBC. THE 2020 CODE IS IN
 EFFECT.
 11) THE EXISTING PLANS FOR THIS SPACE ON FILE WITH THE
 CITY SHOW THE GREASE INTERCEPTOR AS A 100 GPM UNIT BUT
 THE EQUIPMENT SCHEDULE ON SHT. S-2 SHOWS THE GREASE
 INTERCCEPTOR AS 1250 GALLONS. CLARIFY.
 12) INDIATE THE CLASSIFICATION OF WORK ON THE PLANS PER
 FBC-EXISTING BUILDING SEC.601.1. ALSO, INDICATE THE
 COMPLIANCE METHOD PER FBC-EXISTING SEC.301.3.
 13) IT APPEARS THAT A HAND SINK HAS BEEN REMOVED AND
 THE SERVICE SINK RELOCATED BASED ON PLANS FROM THE
 PREVIOUS OCCUPANCY. SUBMIT A WATER AND SANITARY RISER
 DIAGRAM TO SHOW THE CHANGES TO THE SANITARY SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  