Plan Review Notes
Plan Review Notes For Permit 21070232
Permit Number 21070232
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-08 11:11:18JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1 FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL5293-R45 SELECTED SYSTEM NO. W-7 DO NOT MEET
 THE EXPOSURE CATEGORY C; ZONE 2 MINIMUM DESIGN PRESSURE
 REQUIREMENT OF -79.38 OR ZONE 3 MINIMUM DESIGN PRESSURE
 REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM NO. THAT
 MEETS OR EXCEEDS REQUIREMENTS. NO RATIONAL ANALYSIS IS
 PERMITTED FOR THESE SYSTEMS AS PER LIMITATIONS: 5.7.3.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  