Notes |
Date |
Text |
2021-08-05 16:33:28 | 1) PLEASE PROVIDE A DETAIL OF WHAT THIS TENANT DOES. IS | | THERE COOKING AT THIS CATERING SPACE? FBC 107.2.1 | | | | 2) THE FRESH AIR DUCT SUPPLY AHU-2 IS PENETRATING A | | 2-HOUR RATED WALL, PLEASE SHOW HOW YOU WILL PROTECT THE | | RATED PENETRATION AT THIS LOCATION. FBC M 607 | | | | 3) PLEASE ADD A NOTE ON THE DRAWING THAT THE | | REFRIGERATION WILL REQUIRE A SEPERATE PERMIT AND PLAN | | REVIEW AS IT WILL NOT BE REVIEWED WITH THIS PROJECT. | | | | 4) PLEASE ADD A NOTE ON THE DRAWING, IF IT APPLIES, THE | | HOOD WILL REQUIRE A SEPERATE PERMIT AND PLAN REVIEW AS | | IT WILL NOT BE REVIEWED WITH THIS PROJECT. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|