2021-08-10 15:12:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21070155
 ADD: 1609 S. DIXIE HWY.
 CONT: MARION CONSTRUCTION
 TEL: 561-324-3163
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 10TH/ 2021
 ACTION: DENIED
  
 1A) SHEET A000 SITE PLAN. THE SUBMITTED SITE PLAN DOES
 NOT INDICATE THE PROPERTY LINES. PERMIT 19070414 AND
 THE PALM BEACH COUNTY PROPERTY APPRAISERS WEBSITE SHOWS
 THE PARKING LOT ON THE NORTH SIDE OF THE BUILDING ALL
 UNDER ONE PROPERTY CONTROL NUMBER. IS THE LOT BEING
 SUB-DIVIDED OR IS THE PARKING LOT JUST NOT SHOWN? 107.
 2.1.2. ADDITIONAL INFORMATION IS REQUIRED. THE OPENINGS
 ON THE NORTH SIDE OF THE BUILDING VERSES THE LOCATION
 OF THE PROPERTY LINE AND AMOUNT OF ALLOWABLE OPENINGS,
 2020FBC-BUILDING CODE TABLE 705.8. MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION.
  
 1B) THE SITE PLAN A000, AND A100 SHEET SHOWS DOOR 105
 LEADING OUT INTO THE ALLEY. THE LIFE SAFETY PLAN A-106
 SHOWS THIS SAME DOORWAY AS A MEANS OF EGRESS, PLEASE
 PROVIDE WHERE THE PROPERTY LINE IS FOR THE OUTSWING
 DOOR. WHAT WOULD PREVENT A TRUCK FROM PARKING AT THE
 DOORWAY BLOCKING THE MEANS OF EGRESS. SHOW COMPLIANCE
 WITH THE 2020 FBC-BUILDING CODE SECTION 3202.2 DOORS
 AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE PUBLIC
 WAY.
  
 2) SHEET A000 SITE PLAN/ CODE RESEARCH LIST THE
 CLASSIFICATION AS ALTERATION LEVEL 3. PLEASE REVIEW THE
 2020 FBC-EXISTING BUILDING CODE SECTION 505.1 SCOPE.
 LEVEL 3 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS
 50 PERCENT OF THE BUILDING AREA. PLEASE ALSO NOTE THIS
 IS A 2-STORY BUILDING, WHEN FIGURING THE AREA. I
 BELIEVE THIS IS A TENANT BUILD-OUT AND A BUILDING
 PARTIAL CHANGE OF OCCUPANCY AND NEEDS TO SHOW
 COMPLIANCE WITH SECTION 1001.2.2.1 PARTIAL CHANGE OF
 OCCUPANCY SECTION 1012 SHALL APPLY.
  
 3A) SHEET A000 SITE PLAN/ CODE RESEARCH LIST OCCUPANCY
 TYPES M AND S-1 AS NON-SEPARATED OCCUPANCIES AND A
 PORTION OF THE S-1 OCCUPANCY TO CHANGE TO F-1
 OCCUPANCY. THE 3 LISTED OCCUPANCY TYPES M, S-1 &
 F-1 DO NOT REQUIRE OCCUPANCY SEPARATION SEE TABLE 508.4
 2020FBC-B. SHEET A106 THE LIFE SAFETY PLAN THE DESIGNER
 OF RECORD IS DESIGNING THIS TENANT SPACE WITH 2 HOUR
 RATED TENANT SEPARATION WALLS AND 2 HOUR DOORS WITHIN
 THE TENANT SEPARATION WALLS. PLEASE PROVIDE EITHER A UL
 LISTING AND ASSEMBLY FOR THE RATED WALL OR GYPSUM
 ASSEMBLY. 2020 FBC-BUILDING 708.3 FIRE RESISTANCE
 RATING.
  
 3B) THE LIFE SAFETY PLAN A106 & A100 THE CONSTRUCTION
 PLAN BOTH SHOW 2-HOUR FIRE RATED DOORS INTO THE NEXT
 TENANT SPACE, PLEASE PROVIDE THE TYPE OF DOOR AND FRAME
 FOR THIS OPENING. THIS TYPE OF CONSTRUCTION EXCEEDS THE
 CODE REQUIREMENTS, BUT THE DESIGNER WOULD NEED TO MEET
 THE REQUIREMENTS FOR DOOR OPENINGS IN FIRE WALLS TABLE
 716.5 OF THE 2020 FBC-B.
  
 4) THE SUBMITTED SITE PLAN A.000 PLANS SHOW OCCUPANCY
 F-1 KITCHEN/ CATERING BUT WITHIN THE SUBMITTED PLAN
 THERE IS NO OVENS SHOWN FOR BAKING. THERE ARE LARGE
 FLOOR MIXERS, WOOD KNEADING TABLE BUT NO OVENS?
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET A-104 THE NORTH ELEVATION INDICATES WHAT
 APPEARS TO BE A SHELVING UNIT WITH THE 1ST LEVEL OF
 SHELVING AT 36 INCHES ABOVE FINISH FLOOR. 2020
 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) THE SUBMITTED PLANS INDICATE IN THE TITLEBLOCK THEY
 WERE DESIGNED BY ARCHITECT ANGELO DAVILA ARCHITECT LLC.
 THE PLANS ARE NOT SIGNED NOR SEALED. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A DOCUMENT IN
 THE FILE FOLDER, SCANNED, FACSIMILE, DIGITALLY CREATED
 OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT
 BE USED ON DIGITALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  