Plan Review Notes
Plan Review Notes For Permit 21070146
Permit Number 21070146
Review Stop P
Sequence Number 1
Notes
Date Text
2021-07-28 13:04:411) SHT. A3.2 - THE SHOWER WIDTH IS SHOWN AS 2'-6" AND
 ALSO AS 36 INCHES ON THE PLAN. WHICH IS IT? CLARIFY.
 2) SHT. A3.2 - DETAIL #1 - SHOW THE DIMENSIONS OF THE
 BLOCKING AND THE TYPE OF MATERIAL USED FOR THE
 REINFORCEMENT OF THE FUTURE GRAB BARS.WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) SHT. A5.1 - DETAIL #11 - THE SHOWER FLOOR SHALL
 SLOPE A MINIMUM OF 1/4 INCH PER FOOT TO THE DRAIN, NOT
 1/8 OF AN INCH. FBC-PLUMBING SEC. 421.5.2.
 4) SUBMIT FIRESTOPPING DETAILS FOR ANY FLOOR
 PENETRATIONS THAT MAY OCCUR. WPB AMEND. TO FBC SEC.
 107.3.5.1.1(4).
 5) SHT. ALS 1.1 - THE LIFESAFETY PLAN SHOWS AN
 OBJECTNEXT TO THE WATER CLOSET IN THEE PRIVATE TOILET
 ROOM #113 AND ON SHT. A1.5. IDENTIFY THIS OBJECT.IT MAY
 NOT BE PERMITTED TO ENCROACH INTO THE CLEAR FLOOR SPACE
 FOR THE WATER CLOSET.
 6) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 CCOFFEE MAKER, DISHWASHER, ICEMAKER AND
 REFRIGERATOR.FBC-PLUMBING SEC.608.2, 608.17.1.2.
 7) SHT. P3.1 APPEARS TO SHOW THE TANKLESS WATER HEATER
 IN THE SHOWER. CLARIFY. THE IWH SHALL BE INSTALLED IN A
 LOCATION THAT ALLOWS ACCESS FOR MAINTENANCE AND
 REPLACEMENT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  