Plan Review Notes For Permit 21070146 |
Permit Number |
21070146 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-07-28 13:04:41 | 1) SHT. A3.2 - THE SHOWER WIDTH IS SHOWN AS 2'-6" AND | | ALSO AS 36 INCHES ON THE PLAN. WHICH IS IT? CLARIFY. | | 2) SHT. A3.2 - DETAIL #1 - SHOW THE DIMENSIONS OF THE | | BLOCKING AND THE TYPE OF MATERIAL USED FOR THE | | REINFORCEMENT OF THE FUTURE GRAB BARS.WPB AMEND. TO FBC | | SEC. 107.2.1. | | 3) SHT. A5.1 - DETAIL #11 - THE SHOWER FLOOR SHALL | | SLOPE A MINIMUM OF 1/4 INCH PER FOOT TO THE DRAIN, NOT | | 1/8 OF AN INCH. FBC-PLUMBING SEC. 421.5.2. | | 4) SUBMIT FIRESTOPPING DETAILS FOR ANY FLOOR | | PENETRATIONS THAT MAY OCCUR. WPB AMEND. TO FBC SEC. | | 107.3.5.1.1(4). | | 5) SHT. ALS 1.1 - THE LIFESAFETY PLAN SHOWS AN | | OBJECTNEXT TO THE WATER CLOSET IN THEE PRIVATE TOILET | | ROOM #113 AND ON SHT. A1.5. IDENTIFY THIS OBJECT.IT MAY | | NOT BE PERMITTED TO ENCROACH INTO THE CLEAR FLOOR SPACE | | FOR THE WATER CLOSET. | | 6) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE | | CCOFFEE MAKER, DISHWASHER, ICEMAKER AND | | REFRIGERATOR.FBC-PLUMBING SEC.608.2, 608.17.1.2. | | 7) SHT. P3.1 APPEARS TO SHOW THE TANKLESS WATER HEATER | | IN THE SHOWER. CLARIFY. THE IWH SHALL BE INSTALLED IN A | | LOCATION THAT ALLOWS ACCESS FOR MAINTENANCE AND | | REPLACEMENT. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|