Plan Review Notes
Plan Review Notes For Permit 21070073
Permit Number 21070073
Review Stop G
Sequence Number 1
Notes
Date Text
2021-07-08 09:48:1907/08/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CONTRACT STATES FUTURE GAS THAT CONSISTS OF
 RANGE AND BBQ. THESE APPLIANCES NEED TO BE ADDED TO THE
 SYSTEM AND CALCULATED TO SIZE THE MAIN FEED PROPERLY IN
 THE LONGEST RUN. WOULD YOU PLEASE SHOW THE TOTAL BTU'S
 ON ISOMETRIC GAS RISER? LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR RANGE
 AND BBQ. THEY MAY BE A GENERIC TYPE WITH MINIMUM SIZING
 FOR THE FUTURE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE SHOW ON ISOMETRIC DRAWING THE LENGTH OF ALL
 CUT SECTIONS OF PIPE TO THE RANGE AND GIVE THE TYPE OF
 PIPE (EHD NUMBER FOR CSST) PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 5. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A
 ROOF AND IT WILL BE IN A COVERED PATIO. WOULD YOU
 PLEASE PROVIDE THE MANUFACTURER'S RECOMMENDATION FOR A
 VENTILATION HOOD PER THE 2020 FBC RES. SEC? G2408.1.
  
 6. PLEASE SHOW REGULATOR AND ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 7. PLEASE SHOW LABEL THE SHUTOFF VALVE ON GAS ISOMERIC
 PER THE 2020 FBC RES. SEC. G2420.5. THE SHUT OFF INSIDE
 SHALL BE ACCESSIBLE WITHOUT MOVING THE EQUIPMENT PER
 THE 2020 FBC SEC. G2403 (202) GD, ACCESS.
  
 8. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR
 APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC
 RES. SEC. G2419.2.
  
 9. FUTURE GAS APPLIANCE CONNECTION CAPPED AND SHUT OFF
 VALVE INSTALLED PER THE 2020 RES. SECS. G2415, G2422
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  