Plan Review Notes For Permit 21070067 |
Permit Number |
21070067 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-08-10 14:21:06 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, PLEASE PROVIDE THE TEST REPORTS ALONG | | WITH RESULTS FOR THE FLOORING/UNDERLAYMENT APPLIED TO A | | 6" THICK SLAB WITH NO SUSPENDED CEILING AS PER THE | | FOLLOWING: | | | | 1) FBC?B 2020 1207.3 STRUCTURE?BORNE SOUND. | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E?492. | | | | 2) FBC?B 2020 1207.2 AIR?BORNE SOUND. WALLS, | | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR | | AIR?BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E | | 90. | | | | 3) FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED | | AS | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | |
|