2021-08-06 07:22:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SEE PREVIOUS LIST; THE PLAN SUBMITTED DOES NOT SHOW
 COMPLETE SCOPE AND IT APPEARS THAT FIRE RATED WALLS ARE
 AFFECTED (BETWEEN UNITS, CORRIDOR). IT IS NOT CLEAR IF
 THE DRYWALL BEING REPLACED ARE A PART OF A FIRE RATED
 ASSEMBLY.
  
 1. FBC 107 PROVIDE A PLAN THAT SHOWS LOCATION(S) AND
 SCOPE OF WORK. SHOW ALL FIRE RATED WALLS. IF ANY FIRE
 RATED WALLS ARE AFFECTED, PROVIDE A DETAIL, FBC B 703.
  
 DISCUSSED WITH CONTRACTOR OVER TELEPHONE. PER
 CONTRACTOR, CEILINGS ARE ALSO AFFECTED. NOTES ON THE
 PLAN SUBMITTED AND COPIES OF THE RATED ASSEMBLIES FROM
 THE ORIGINAL BUILDING PLANS SHOULD SUFFICE.
  
 (NEW COMMENT)
 2. VALUE APPEARS LOW BASED ON WORK DESCRIPTION PROVIDED
 OVER THE TELEPHONE.
  
  
  
  