2021-07-23 14:35:03 | 2ND REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT-21061866 |
| 7/23/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. THE 1ST REVIEW COMMENTS 1- |
| 14 COPIED BELOW WERE NOT ADDRESSED. IN RESPONSE A |
| GENERIC TANKLESS WATER HEATER PIPING DIAGRAM AND PIPE |
| SIZING TABLE FROM WHAT APPEARS TO BE A WH MANUAL WERE |
| UPLOADED. PLEASE COMPLY WITH THE COMMENTS.IF YOU NEED |
| FURTHER ASSISTANCE PLEASE CONTACT ME- SEE INFO BELOW. |
| |
| 1- SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES |
| SECS. G2413.4.1, G2413.4.2. |
| 2- SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 3- TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4- SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC. |
| 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| 5- INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020 |
| FBC FUEL GAS RES. SEC. G2413.2. |
| 6- SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC. |
| G2413.4.1. |
| 7- SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR |
| 2020 FBC FUEL GAS RES. SEC. G2408.1. |
| 8- SUBMIT MANUFACTURE'?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2020 FBC FUEL GAS SEC.410.1 OR 2020 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 9- THE COPY OF GAS TABLE 000.00 IS FROM AN OUTDATED |
| FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS THE 2020 |
| FBC FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT SIZING |
| TABLE. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| 10- INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER |
| IS THE ONLY GAS APPLIANCE IN THIS SYSTEM? IF NOT, |
| SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES, |
| TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS |
| OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE |
| SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE |
| SYSTEM. THESE REQUIREMENTS ALSO APPLY TO A NEW GAS |
| SYSTEM. WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| RESIDENTIAL GAS |
| 11- A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION, WPB AMENDMENTS TO THE FBC SEC. 105.1 |
| 12- SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION |
| OF THE TANKLESS WATER HEATER AND THE LOCATION AND |
| DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND DRAWN. WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 13- INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER |
| IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| ON THE APPLICATION IN THE DESCRIPTION OF WORK. WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS |
| |
| 14- WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6695 |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS ST. |
| WEST PALM BEACH, FL. 33401 |
| 561-805-6719 |
| [email protected] |
| |