2021-07-14 13:49:56 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21061862 |
| 7/14/2021 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES |
| SECS. G2413.4.1, G2413.4.2. |
| 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 3) TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. |
| 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| 5) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC FUEL GAS |
| SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| THROUGH 402.4 (37) OR 2020 FBC FUEL GAS RES. SEC. |
| G2413. |
| 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020 |
| FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2020 |
| FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| 7) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020 |
| FBC FUEL GAS RES. SEC. G2413.2. |
| 8) SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR |
| 2020 FBC FUEL GAS RES. SEC. G2408.1. |
| 9) NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE DRYER |
| AND GENERATOR. SHOW ON GAS ISOMETRIC. APPLIANCE SHUTOFF |
| 2020 FBC FUEL GAS RES. SEC. 409.5, APPLIANCE CONNECTION |
| 2020 FBC FUEL GAS RES. SEC. 404.15, 411. |
| 10) THE COPY OF GAS TABLE IS FROM AN OUTDATED FUEL GAS |
| CODE. THE FUEL GAS CODE IN EFFECT IS THE 2020 FBC FUEL |
| GAS. SUBMIT A CURRENT COPY OF THE CORRECT SIZING TABLE. |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |